The UN Sustainability Goals address measures to reduce environmental pollution. Water distribution systems (WDSs) use electric energy, which pollutes the atmosphere through, at least partly, the burning of coal. This study simulates, through modeling, variable-speed pumps (VSPs) on 15 different real WDSs on the network solver EPANET and analyzes the payback period. An algorithm is introduced here to select the optimal pump speed pattern to save the most energy while satisfying the constrain of sufficient pressure at all times and all locations. It was found that five of the 15 systems operated unsuccessfully using a VSP, due to the VSP operating at lower speeds causing a lower pressure than normal, thereby causing the pressure to become negative. Additionally, a new chart that compares the payback period, project life, and energy costs between the base case and the VSP case was developed and different regions on the chart reflect different decision criteria.

  • VSPs can save energy in a water system.

  • However, VSPs does not always save energy.

  • Thus, do not install VSPs if there is not enough pressure everywhere in the system.

  • Installing a VSP may or may not pay for itself over the lifetime of the pump.

  • Saving energy may be worth considering it for reducing climate change, effects even though the costs are not recovered.

The United Nations Sustainable Development Goals point to ways to improve our world and include goals that are related to improving the environment and providing clean drinking water for improved public health. Specifically, Goal 3 Good Health and Well-Being talks about the importance of clean water for drinking, Goal 6 Clean Water and Sanitation talks about the importance of water distribution to provide clean water close to people's homes, Goal 7 Affordable and Clean Energy speaks to using clean energy for all uses, including water distribution pumping, Goal 11 Sustainable Cities and Communities involves using less energy, and Goal 13 Climate Action relates to using less coal-based electricity (United Nations 2021).

Global climate change (GCC) results from the burning of fossil fuels to generate electricity, thereby trapping in the sun's heat due to the release of greenhouse gasses such as carbon dioxide and methane (IPCC 2021). Since coal is widely used for electricity generation, reducing the amount of energy consumption can slow down climate change.

Water distribution systems (WDSs) involve pumping water from lower elevations such as a river, lake, or groundwater aquifers, up to a higher elevation where users need the water. Water is pumped through pipes, stored in tanks for storage when users consume water in varying amounts throughout the day and night in a user-demand pattern. Pumps can operate at a constant speed and be turned off and on when storage tank's water levels reach specified set points, both maximum and minimum. Typical controls specify turning the pump(s) off when the tank water level approaches the tank top and off when the tank is almost empty. These operational controls can impact system performance, water quality, and energy efficiency (Jones & Sowby 2014), especially with demand charges and electricity tariffs (McCormick & Powell 2003). Pumps use electricity that can be charged at a constant rate or at a variable rate by the electricity provider (Walski & Vitter 2017). Users typically use more water during the daytime when they are awake and almost no water at night when they are sleeping. In contrast to constant-speed pumps, variable-speed pumps (VSPs) change the speed of the pump as needed throughout the day and night to match demand. They have been recommended to reduce the amount of energy used since there are times when the pump speed is lower and, therefore, saving energy (Steger & Pierce 2018; Qandil et al. 2019; Cimorelli et al. 2020). VSPs can be used to match desired pressure values at various locations and times in the WDS (Wu et al. 2009).

Payback period (PP) is an econometric method of quantifying whether or not an action is worthwhile. PP is quantified by calculating how long it takes for the savings realized from an action to payback the initial financial investment. If the PP is less than the time to make an additional investment, then the action results in a financial profit. Conversely, if the initial investment is not paid off before another financial investment is required, the action never pays for itself and, therefore, is not worth it. In the context of WDSs and VSP, if the energy cost savings from installing a VSP is not realized within the lifetime of a VSP, then installing a VSP is not worth it and vice versa.

Page et al. (2019) studied VSPs in a system in a single WDS in South Africa and showed that pressure values were kept low and relatively constant. Cimorelli et al. (2020) used a genetic algorithm to optimize pump speeds on two portions of a WDS and found that VSPs could save energy in that system but do not always justify the costs. Abdallah & Kapelan (2019) studied a VSP optimization method for a single system to optimize both energy cost and water quality but not the economic aspects of whether or not the initial investment pays off and found that VSPs can save energy and improve water quality. Briceño-León et al. (2021) investigated different control strategies for fixed and VSPs and found that the number and type of pumps affect the control system and is, therefore, system-specific. No mention was made, however, if the installation of a VSP paid off economically. Darweesh (2018) investigated using VSPs for reducing energy costs and leakage on a single simplified system and found that a 20% reduction is possible. Bonvin et al. (2021) used a linear programming/non-linear programming (LP/NLP)-based branch and bound algorithm to optimize pump scheduling. In addition, rotational speed related to pumps used as turbines (Alberizzi et al. 2018; Tahani et al. 2020; Ebrahimi et al. 2021) is a related and emerging idea but separate in scope from the present study. Energy savings in WDSs can also result from changing reservoir level (Kraft & Barkdoll 2020), tank location (Wang & Barkdoll 2017), using biofuel (Archer & Barkdoll (2017), pipe enlargement (Barkdoll et al. 2015), and tank parameters pumping station properties (Ghimire & Barkdoll 2010).

The purpose of this study is to determine what factors determine when VSPs are more efficient than constant-speed pumps and are economically profitable for a large number and variety of WDSs. In addition, if VSPs are more energy-efficient, then this could reduce energy use and reduce environmental impacts related to energy use and, therefore, help attain the United Nations Sustainable Development Goals.

System description

Fifteen WDSs were chosen to test whether VSPs improved the energy costs of the systems. The WDSs ranged from branched to loop systems, those with and without valves and tanks (Table 1 and Figures A1 through A15 in Appendix A). All systems had time-varying user demand patterns at most junctions and pump on/off controls related to elevated storage tank water levels. All the systems' modeling information was obtained through personal communications with various researchers. The town identities are removed for security purposes. They all represent realistic WDSs. Energy costs and demand charges were already included for the region in which the WDS is located and remained unaltered during this study.

Table 1

System characteristics

SystemJunctions (#)Pipes (#)Pumps (#)Reservoirs (#)Tanks (#)Valves (#)
41 41 
126 168 
118 135 
348 395 
874 958 
12,525 14,824 
93 118 
25 25 
10 44 62 
11 115 115 
12 19 40 
13 504 551 
14 15 15 
15 388 429 11 
SystemJunctions (#)Pipes (#)Pumps (#)Reservoirs (#)Tanks (#)Valves (#)
41 41 
126 168 
118 135 
348 395 
874 958 
12,525 14,824 
93 118 
25 25 
10 44 62 
11 115 115 
12 19 40 
13 504 551 
14 15 15 
15 388 429 11 

Simulation procedure

All simulations were extended-period simulations (Duan et al. 2020) in the network solver EPANET, which takes values of reservoir level, pipe diameter, lengths, roughness values, junction elevations, and tank size and location and calculates the flow in every pipe and the pressures at every junction for all times steps (EPA 2021). Simulations were performed in which the demands, flows, pressures, and tank levels changed every time step. First, to get the base case energy cost, the simulation was run for an unaltered system with pump speed factors of 1.0 for every time step and the energy cost was recorded. A speed value of 1.0 denotes a speed unchanged from the base case.

The pump speed factor determination algorithm used here was based on the logic that the pump speed should be proportional to the demand pattern (Georgescu et al. 2014), since EPANET uses a demand-driven modeling approach. First, the pump speed pattern was exactly proportional to the user demand pattern but was then adjusted to save the most energy and ensure adequate pressures at all nodes at all times. Adequate pressures were considered to be greater than 20 psi, (Nowak et al. 2018). This was accomplished using Equation (1). The x value from Equation (1) is a chosen value for each system and the lower the x value the closer the speed multiplier will be to the base case value of 1.0. Therefore, the algorithm starts with the pump speed factors equal to the user demand patterns factors. For each subsequent attempt at choosing the pump speed factors, each factor is adjusted toward the ‘all 1.0’ base case values by some proportion, as denoted by x in Equation (1). If the pressure at any junction or any time goes negative, then the pump speed factor for that time step is increased to bring the pressure back to a positive value. The set of pump speed factors that result in the minimum energy usage, subject to the positive-pressure constraint is selected.
(1)
  • here i is the time step, 1–24 h, j is the algorithm iteration until the minimum energy cost is found, and F is the pump speed factor.

Several speed patterns with varying values of x were run with each system to determine which would give the lowest energy cost. Once these simulations were run on all the systems, the PP of installing VSPs into the systems was calculated. A price for a variable-speed drive box was determined from research on manufacturers’ websites (Grainger 2021) and some systems needed new, larger pumps to run a variable-speed pump pattern (Pump Products 2021). For the PP calculation, the initial cost for a VSP is either the initial cost for the drive box and/or the new pump. The savings is determined by the cost of running the base case minus the cost of running a VSP. Then the amount of time to payback the investment of a VSP can be found. Inflation of 5% was added for each year of economic costs (Cimorelli et al. 2020). The lifetime of the pump was assumed to be 12 years (Hydraulic Institute 2001). If the VSP cost was not recovered within the VSP lifetime, then installing a VSP is not worth it because it will never payback the initial investment and lose money. Additionally, the amount of time the pumps are on for both the base case and the VSP case were recorded, since using a VSP may slow down the pump enough so that it can never fill the tank and trigger the control command to shut off the pump, thereby potentially using more energy. The algorithm was applied to the existing pump(s) with no more or fewer pumps added or removed, for simplicity, although this would affect the results. Altering the number and locations of pumps, or the operations would require a more comprehensive framework and should be considered for future work.

The initial cost for all the systems when determining the PP was either the cost of a drive box to make a VSP pumping schedule or some systems needed to upsize the pump(s) size to run a variable pumping schedule. The drive box is a Variable Frequency Drive: 480 V with a 50 hp maximum output. 50 hp pumps can operate most of the systems and some can operate on lower horsepower. The four systems that needed a pump upsize are Systems 5, 6, 7, and 8. System 5 had three pumps that needed to be upsized and 20 hp pumps were sufficient to run the system. Each pump costs $9,352. System 6 had one pump that needed to be upgraded and that system needed a size of 50 hp at a cost of $20,100. System 7 also needed a 50 hp pump for the upsize. System 8 needs a 0.33 hp pump upsize which will cost $1,683. The pumps compared for the PP analysis were centrifugal booster pumps and the maximum cost was used for the PP calculations.

After running the 15 systems, it was found that VSPs are not always the best option for all systems, i.e., there are some systems where it costs more energy to run a VSP than it would be for a single-speed pump. This was determined by the PP calculations and the annual costs to run the pumps (Appendix B). The energy costs were found from the EPANET simulation of the systems. Ten of the systems had a PP shorter than the VSP lifetime of 12 years, thereby indicating that installing a VSP would be worth it, while the other five systems never paid back within the pump lifetime. The five systems that did not payback soon enough were all systems where VSPs were less cost-effective than a normal pump system. In short, counterintuitively, sometimes installing a VSP results in increased energy usage. Four of the pumping systems had to have new pumps installed because when the system switched to VSP it was no longer able to provide the requisite pressure that the system needed. The costs of the new pumps were included in the calculation of the PP and one of those four systems will not payback during the pump lifetime. From looking at the systems, one of the criteria for not installing a VSP is that if the pressure is slightly over 20 psi at any junction at any time in the system, then the pump should not be changed out for a VSP because the pump will need to be upsized to meet the demand of the system. If a pump is already being swapped out in a regular maintenance schedule, then this may no longer apply if the cost of upsizing can be paid off in time.

As stated previously, an interesting result from running the simulations is the fact that some of the pumps did not reduce PP when running on a VSP schedule. To investigate this, different factors were studied to see what could be affecting the energy use to increase the cost (Table 2). The first to be considered is the difference between the time the pump is on between the VSP case and the base case. The reason was that if the VSP was turned on longer than a normal pump, then that would lead to an increase in energy cost. However, the percent of time being turned on for all the VSP systems was greater than the normal case and several reached 100% time on for the VSP, and those cases all paid off. There was no correlation between the percent of time the VSP was on and whether it would be cost-effective or not. Another attribute of the systems was the size of the storage tanks with the thought the larger the diameter of the tank the longer it would take to fill and, therefore, have the pump running longer to reach the upper set point at which the pump would switch off. There was also no correlation between tank sizes and if a system would fail to payback or not. The five systems that could not payback had a variety of tank sizes and number of tanks and Systems 12 and 13 both had no tanks at all. One final parameter of the systems that was considered to determine what caused the failure in the PP was the average flow being pumped into the system for both the base case and the variable-speed trial. For most of the systems, the variable-speed schedule generated a greater average flow than the base case average flow. Additionally, Systems 10, 12, and 13 had an average flow for the VSP trial less than the average flow for the base case. No conclusions can be drawn from this result since there are differences between the three systems that make comparison difficult.

Table 2

VSP and base case comparison

SystemPayback period (years)Use VSP?% Time on, base case% Time on, VSPTank diameter/s (ft)AVG flow, base case (GPM)AVG flow, VSP case (GPM)Upsize pump?
Yes 75 100 50 293 645 No 
18 No 16 66 No 
Infinity No 50 100 186
106 
2,388 37,041 No 
Yes 27 100 58 368 476 No 
Yes 48 100 35 1,037 3,148 Yes 
Infinity No 47 92 14 843 6,145 Yes 
Yes 36 87 100 16,314 61,439 Yes 
Infinity No 8, 100 100, 87 85,
50,
164 
3,397 12,995 Yes 
12 Maybe 65 82 25 36 51 No 
10 Yes 64 100 80 621 597 No 
11 93 No 17 99 86 No 
12 Infinity No 100 57 None 4,211 3,844 No 
13 Infinity No 100 100 None 316 204 No 
14 Yes 44 No 
15 Yes 100 100 31, 21, 14, 12, 12, 8, 7 166 299 No 
SystemPayback period (years)Use VSP?% Time on, base case% Time on, VSPTank diameter/s (ft)AVG flow, base case (GPM)AVG flow, VSP case (GPM)Upsize pump?
Yes 75 100 50 293 645 No 
18 No 16 66 No 
Infinity No 50 100 186
106 
2,388 37,041 No 
Yes 27 100 58 368 476 No 
Yes 48 100 35 1,037 3,148 Yes 
Infinity No 47 92 14 843 6,145 Yes 
Yes 36 87 100 16,314 61,439 Yes 
Infinity No 8, 100 100, 87 85,
50,
164 
3,397 12,995 Yes 
12 Maybe 65 82 25 36 51 No 
10 Yes 64 100 80 621 597 No 
11 93 No 17 99 86 No 
12 Infinity No 100 57 None 4,211 3,844 No 
13 Infinity No 100 100 None 316 204 No 
14 Yes 44 No 
15 Yes 100 100 31, 21, 14, 12, 12, 8, 7 166 299 No 

This study found that not every system is more cost-effective when using a VSP, which concurs with Cimorelli et al. (2020). From these results, guidelines of when to install VSPs and when not to were investigated by looking at different parameters of the systems. One aspect determined is that if the pressure in a system is slightly above 20 psi anytime or anywhere, then a VSP should not be installed. Additionally, factors such as tank size, percent time the pumps are on, and the average flow from the pumps do not influence if a pumping system will payback the VSP investment or not. The recommendation for water managers thinking about installing a VSP would be to perform an analysis of their own system. First, make a pump speed schedule using the equation developed in this paper and apply different variations to find the optimal conditions of the VSP. From there, conduct a PP analysis, then plot the results on the graph below (Figure 1). The quadrants are divided along the 1.0 line for both axes. The lower left quadrant denotes a system in which a VSP will pay off and also reduce greenhouse gas emissions. The lower left is where the PP is short and the energy of running the pump is also low. This is the ideal section of the chart for a system installing VSP to be. The upper right quadrant has long PPs and higher energy costs for running the pumps. This section is when a VSP should never be installed because both factors are non-ideal. The upper left quadrant is where there are long PPs but the energy cost of running the pumps is low. This section may not be the best economically but since the pump will require less energy to run, the environmental impacts of high energy use will be reduced; thus, depending on the goals of the system managers installing the pump, VSPs may be considered. The lower right quadrant is where there are short PPs and high energy costs. Systems in this quadrant will save money but use more energy which will increase environmental impacts. This is another decision that the managers of the system will need to make. However, none of the tested systems ended up in this section, so this may be a rare section due to the relationship between energy cost and energy usage. More energy usage will lead to more costs, making a PP less than the VSP lifetime harder to attain.

Figure 1

Graph of PP/project lifetime vs. E/Eo to aid in deciding whether to replace a constant-speed pump with a VSP. Systems that plot closer to origin with E/Eo and PP/project lifetime values <1.0 indicate the efficacy of installing a VSP.

Figure 1

Graph of PP/project lifetime vs. E/Eo to aid in deciding whether to replace a constant-speed pump with a VSP. Systems that plot closer to origin with E/Eo and PP/project lifetime values <1.0 indicate the efficacy of installing a VSP.

Close modal

All relevant data are included in the paper or its Supplementary Information.

Abdallah
M.
&
Kapelan
Z.
2019
Fast pump scheduling method for optimum energy cost and water quality in water distribution networks with fixed and variable speed pumps
.
Journal of Water Resources Planning and Management
145
(
12
).
doi: 10.1061/(ASCE)WR.1943-5452.0001123
.
Archer
A.
&
Barkdoll
B. D.
2017
Energy savings using biofuel in a developing-country water distribution system
.
Water Science and Technology: Water Supply
18
(
1
).
doi: 10.2166/ws.2017.221
.
Barkdoll
B.
,
Murray
K.
,
Sherrin
A.
,
O'Neill
J.
&
Ghimire
S.
2015
Effective-power-ranking algorithm for energy and greenhouse gas reduction in water distribution systems through pipe enhancement
.
Journal of Water Resources Planning and Management
,
06015001
.
doi: 10.1061/(ASCE)WR.1943-5452.0000568
.
Bonvin
G.
,
Demassey
S.
&
Lodi
A.
2021
Pump scheduling in drinking water distribution networks with an LP/NLP-based branch and bound
.
Source: Optimization and Engineering
22
(
3
),
1275
1313
.
Briceño-León
C. X.
,
Iglesias-Rey
P. L.
,
Martinez-Solano
F. J.
,
Mora-Melia
D.
&
Fuertes-Miquel
V. S.
2021
Use of fixed and variable speed pumps in water distribution networks with different control strategies
.
Water (Switzerland)
13
(
4
).
doi: 10.3390/w13040479
.
Darweesh
M.
2018
Assessment of variable speed pumps in water distribution systems considering water leakage and transient operations
.
Journal of Water Supply: Research and Technology – AQUA
67
(
1
),
99
108
.
doi: 10.2166/aqua.2017.086
.
Duan
H.-F.
,
Pan
B.
,
Wang
M.
,
Chen
L.
,
Zheng
F.
,
Zhang
Y.
,
Duan
H.-F.
,
Pan
B.
,
Wang
M.
,
Chen
L.
,
Zheng
F.
&
Zhang
Y.
2020
State-of-the-art review on the transient flow modeling and utilization for urban water supply system (UWSS) management
.
Journal of Water Supply: Research and Technology – AQUA
69
(
8
),
858
893
.
https://doi.org/10.2166/aqua.2020.048
.
Ebrahimi
S.
,
Riasi
A.
&
Kandi
A.
2021
Selection optimization of variable speed pump as turbine (PAT) for energy recovery and pressure management
.
Energy Conversion and Management
227
.
doi: 10.1016/j.enconman.2020.113586
.
EPA
2021
EPANET Application for Modeling Drinking Water Distribution Systems
.
U.S. Environmental Protection Agency
.
Georgescu
A.-M.
,
Coşoiu
C. L.
,
Sorin
P.
,
Georgescu
S.-C.
,
Valer
H. L.
&
Anton
A.
2014
Estimation of the efficiency for VSPs in EPANET compared with experimental data
.
Procedia Engineering
89
,
1404
1411
.
doi: 10.1016/j.proeng.2014.11.466
.
Ghimire
S. R.
&
Barkdoll
B. D.
2010
Sensitivity analysis of municipal drinking water distribution system energy use to system properties
.
Urban Water Journal
7
(
4
),
1744
9006
.
Pages 217–232
.
Hydraulic Institute
2021
Pump Life Cycle Costs: A Guide to LCC Analysis for Pumping Systems: Executive Summary, DOE/GO-102001-1190, Hydraulic Institute, Europump, U.S. Department of Energy January 2001
.
IPCC
2021
AR6 Climate Change 2021: The Physical Science Basis. The Intergovernmental Panel on Climate Change
.
Jones
J. C.
&
Sowby
R. B.
2014
Water system optimization: aligning energy efficiency, system performance, and water quality
.
Journal AWWA
106
(
6
),
66
71
.
doi: 10.5942/jawwa.2014.106.0087
.
Kraft
L.
&
Barkdoll
B. D.
2020
Effect of reservoir elevation on energy consumption in water distribution systems
.
Urban Water Journal
.
doi: 10.1080/1573062X.2020.1758165
.
McCormick
G.
&
Powell
R. S.
2003
Optimal pump scheduling in water supply systems with maximum demand charges
.
Journal of Water Resources Planning and Management
129
(
5
).
doi: 10.1061/(ASCE)0733-9496(2003)129:5(372)
.
Nowak
D.
,
Krieg
H.
,
Bortz
M.
,
Geil
C.
,
Knapp
A.
,
Roclawski
H.
&
Böhle
M.
2018
Decision support for the design and operation of VSPs in water supply systems
.
Water
10
(
6
),
734
.
doi: 10.3390/w10060734
.
Page
P. R.
,
Zulu
S.
&
Mothetha
M. L.
2019
Remote real-time pressure control via a variable speed pump in a specific water distribution system
.
Journal of Water Supply: Research and Technology – AQUA
20
28
.
doi: 10.2166/aqua.2018.074
.
Qandil
M. D.
,
Abbas
A. L.
,
Al-Haddad
M. R.
&
Amano
R. S.
2019
Energy consumption, energy-saving and emissions reduction of wastewater treatment plants (WWTPs) in Wisconsin
.
AIAA Propulsion and Energy Forum and Exposition
.
November 2019, Conference: AEE World 2019
.
Steger
P.
&
Pierce
D.
2018
Centrifugal pumps and variable-frequency drives: a match made in heaven?
Opflow
44
(
12
),
10
14
.
https://doi.org/10.1002/opfl.1111
.
Tahani
M.
,
Kandi
A.
,
Moghimi
M.
&
Houreh
S. D.
2020
Rotational speed variation assessment of centrifugal pump-as-turbine as an energy utilization device under water distribution network condition
.
Energy
213
(
15
).
doi: 10.1016/j.energy.2020.118502
.
United Nations
2021
Sustainable Development, The 17 Goals
.
Available from: https://sdgs.un.org/goals.
Walski
T.
&
Vitter
S.
2017
Beware of demand charges
.
Opflow
43
(
12
),
22
23
.
doi: 10.5991/OPF.2017.43.0082
.
Wu
Z. Y.
,
Tryby
M.
,
Todini
E.
&
Walski
T. M.
2009
Modeling variable-speed pump operations for target hydraulic characteristics
.
Journal AWWA
101
(
1
),
54
64
.
doi: 10.1002/j.1551-8833.2009.tb09823.x
.
This is an Open Access article distributed under the terms of the Creative Commons Attribution Licence (CC BY 4.0), which permits copying, adaptation and redistribution, provided the original work is properly cited (http://creativecommons.org/licenses/by/4.0/).

Supplementary data