Legionnaires’ disease (LD) is a severe pneumonia mainly caused by the bacterium Legionella pneumophila. Although many environmental sources of LD have been described, the sources of the majority of non-outbreak LD cases have not been identified. In several outbreaks in the Netherlands, wastewater treatment plants (WWTPs) were identified as the most likely source of infection. In this study, four criteria for Legionella growth and emission to air and surface waters were selected based on the literature and a risk matrix was drafted. An inventory was made of all WWTPs and their characteristics in the Netherlands. The risk matrix was applied to identify WWTPs at risk for Legionella growth and emission. Wastewater was collected at WWTPs with moderate to high risk for Legionella growth and emission. In 18% of the sampled WWTPs, Legionella spp. was detected using culture methods. The presented risk matrix can be used to assess the risks of Legionella growth and emission for WWTPs and support surveillance by prioritizing WWTPs. When Legionella is detected in the wastewater, it is recommended to take action to prevent emission to air or discharge on surface waters and, if possible, reduce the Legionella concentration.

  • The developed risk matrix to assess the risks of Legionella growth and emission from WWTPs supports prioritizing WWTP for Legionella surveillance.

  • Legionella spp. was detected in 18% of the WWTP with moderate to high risk.

  • This work contributed to the development of a guidance document to support owners of WWTPs to identify and control Legionella risks.

Legionnaires’ disease (LD) is a severe pneumonia mainly caused by Legionella pneumophila. In the Netherlands, the LD incidence increased in recent years (Reukers et al. 2019). Legionella bacteria can occur naturally in water and soil, often in low concentrations (Steinert et al. 2002). Higher concentrations are sometimes observed in water installations, such as building water systems, wet cooling towers and whirlpools, because the temperature is more favorable for growth and competition from other bacteria is lower (Steinert et al. 2002). Although many possible and confirmed environmental sources of LD have been described (van Heijnsbergen et al. 2015), a source of infections cannot be identified for the majority of sporadic (non-outbreak) cases. In the Netherlands, potential sources were systematically sampled as part of source-finding investigations, of which the majority of sampled sources were drinking water systems. Between 2002 and 2012, all potential sources of exposures were sampled for 392 non-outbreak patients from whom a clinical isolate was available, and the clinical and environmental isolates were compared using sequence-based typing. Only for 11% of these patients a genotypic match between the clinical isolate and the environmental isolate was found, showing that the source of infection remained unknown for the majority of patients, despite systematic source investigations. Moreover, there appears to be a mismatch in the Netherlands between the sequence types (STs) found in isolates from patients and environmental isolates from drinking water systems (Euser et al. 2013; Den Boer et al. 2015). The L. pneumophila serogroup 1 strain detected most frequently in sampled water systems was the strain ST1, but this strain was found in only a small portion (4–5%) of all clinical isolates. On the other hand, the ST-type of the L. pneumophila isolates found most frequently in patients (ST47) was not found in the sampled tap water systems at all (Euser et al. 2013; Den Boer et al. 2015). These data indicate that important sources of infections were not yet included in the source investigations and suggest that other sources of Legionella are present in the environment, that are causing LD.

In 2017, a wastewater treatment plant (WWTP) at a food processing company was identified as the likely source of contamination for a local increase of pneumonia caused by L. pneumophila observed (Loenenbach et al. 2018). In this installation, high Legionella concentrations were detected in the wastewater of an identical ST as found in five patients: L. pneumophila serogroup 1 ST1646. Another LD cluster with 54 patients could be linked to an industrial WWTP located at a rendering company (Loenenbach et al. 2018; Reukers et al. 2018). Both WWTPs had a biological process which treated nutrient-rich process water at temperatures between 30 and 35 °C (Loenenbach et al. 2018). Other studies also reported LD in employees or local residents in which WWTPs may have played a role (Nguyen et al. 2006; Nygård et al. 2008; Kusnetsov et al. 2010; Olsen et al. 2010; Maisa et al. 2015; Nogueira et al. 2016).

In several studies, Legionella was detected in wastewater samples using culture and/or molecular methods (Allestam et al. 2006; Blatny et al. 2008; Schalk et al. 2012; Lund et al. 2014; Loenenbach et al. 2018). High concentrations (up to 109 colony forming units (CFUs)/L) of L. pneumophila have been detected in the aeration tanks of industrial WWTPs (iWWTPs; Olsen et al. 2010; Loenenbach et al. 2018). During the wastewater treatment process, aerosols are formed, which may disperse Legionella from WWTPs to the environment. In air samples at WWTPs Legionella bacteria were found, with concentrations of up to 3,300 CFU/m3 directly above aeration tanks (Medema et al. 2004; Blatny et al. 2008; Loenenbach et al. 2018). Air measurements showed that aerosols contaminated with Legionella emitted from the aeration tanks can spread through the air over a distance of at least 3 km (Reukers et al. 2018). Vermeulen et al. (2021) showed that exposure to aerosols from WWTPs likely caused LD in residents living near WWTPs. Legionella may also be discharged to surface waters through contaminated WWTP effluent (Olsen et al. 2010; Nogueira et al. 2016; Loenenbach et al. 2018). In the Netherlands, an overview of all WWTPs is missing and no legal requirements are in place for monitoring Legionella at WWTPs. To better understand the contribution of WWTPs to LD more information on the amount, location and characteristics of WWTPs as well as the presence of Legionella in the installations is needed.

In this study, an inventory was made of WWTPs. Furthermore, we developed a risk matrix to identify and prioritize WWTPs in the Netherlands at risk for Legionella growth and emission. Legionella spp. and L. pneumophila were quantified in process water of moderate to high risk WWTPs employing culture methods.

Risk matrix

In 2019, a literature study was performed to identify risk criteria associated with Legionella growth and emission from WWTPs (Bartels et al. 2019). Peer-reviewed English-language articles describing WWTPs that were recognized as the direct or indirect source of Legionella infections were selected. In eight case studies, four similar characteristics were described that may have led to Legionella growth and emission to air and surface waters from WWTPs (Gregersen et al. 1999; Isozumi et al. 2005; Allestam et al. 2006; Nguyen et al. 2006; Blatny et al. 2008; Kusnetsov et al. 2010; Olsen et al. 2010; Maisa et al. 2015; Nogueira et al. 2016; Loenenbach et al. 2018). These characteristics were considered criteria for increased risk, as listed below.

Type of WWTP (biological or non-biological)

All WWTPs described in the case studies were biological WWTPs using aerobic bacteria for wastewater treatment. These bacteria have similar requirements for optimal growth as Legionella bacteria, including oxygen demand (via aeration) and temperature. Legionella growth is not inhibited or outcompeted by these bacteria (Caicedo et al. 2019). Non-biological WWTPs were not described in the literature as a source of LD.

Type of industry

Relevant industries for Legionella growth are industries where many organic compounds such as proteins, and nutrients such as phosphorus and ammonia are discharged into the wastewater. This organic/nutrient-rich wastewater is beneficial for Legionella growth, and high Legionella concentrations have been detected in this water (Caicedo et al. 2019). The following industries with organic/nutrient-rich wastewater were linked to patients with legionellosis:

These types of industries were included in the risk matrix (Table 1). The occurrence or growth of Legionella in treatment plants from other industrial sectors cannot be excluded, including WWTPs receiving wastewater from other industries. However, no case studies for these industries were described at the time of this study, and therefore, the risks for Legionella growth and emission in these other industries are classified as ‘unknown’.

Table 1

Risk matrix for Legionella growth and emission from WWTPs in the Netherlands

Type of WWTPType of industry from which wastewater is treatedTemperature process waterAerationRisk category for emission to airRisk category for emission to surface waters
Biological 
  • Food industry

 
30–38 °C Yes High High 
 
  • Paper and wood

 
 No Moderate  
 
  • Rendering companies

 
25–29 °C or Yes Moderate Moderate 
 
  • Petrochemical

 
39–45 °C No Low  
 
  • Communal WWTPa

 
< 25 °C or >45 °C Yes Low Low 
   No Very low  
 Other industriesb 25–45 °C Yes Unknown Unknown 
   No   
  < 25 °C or >45 °C Yes Unknown Unknown 
   No   
Non-biological Not relevant Not relevant Not relevant Very low Very low 
Type of WWTPType of industry from which wastewater is treatedTemperature process waterAerationRisk category for emission to airRisk category for emission to surface waters
Biological 
  • Food industry

 
30–38 °C Yes High High 
 
  • Paper and wood

 
 No Moderate  
 
  • Rendering companies

 
25–29 °C or Yes Moderate Moderate 
 
  • Petrochemical

 
39–45 °C No Low  
 
  • Communal WWTPa

 
< 25 °C or >45 °C Yes Low Low 
   No Very low  
 Other industriesb 25–45 °C Yes Unknown Unknown 
   No   
  < 25 °C or >45 °C Yes Unknown Unknown 
   No   
Non-biological Not relevant Not relevant Not relevant Very low Very low 

aIn WWTPs without an elevated water temperature (<25 °C), very high concentrations of Legionella may present when wastewater is received from industries with high concentration of Legionella (influent).

bNo case studies were available for other industries and therefore the risk is unknown. However, it cannot be ruled out that other industries with nutrient-rich influent might have an increased risk.

Temperature of the process water

L. pneumophila grows within a temperature range from approximately 25 to 45 °C with an optimum between 35 and 37 °C (Wadowsky et al. 1985; Falkinham et al. 2015). WWTPs that were directly or indirectly identified as the source of LD all had a wastewater temperature between 30 and 37 °C, mainly between 35 and 37 °C (Allestam et al. 2006; Kusnetsov et al. 2010; Olsen et al. 2010; Loenenbach et al. 2018). Based on these case studies, water temperatures between 30 and 38 °C were considered as high risk for Legionella growth. For water temperatures between 25 and 29 °C and between 39 and 45 °C, the risk was categorized as moderate. When the water temperature at a WWTP is always below 25 °C, L. pneumophila growth to high concentrations is unlikely (low risk). However, WWTPs with water temperatures below 25 °C may receive wastewater with high Legionella concentrations (influent). Furthermore, some other Legionella spp. besides L. pneumophila may be able to multiply at these low temperatures. For water temperatures higher than 45 °C, Legionella growth was categorized as possible. These temperature ranges were included in Table 1 as well as their indicative risk level.

Aeration

Aeration of wastewater in aeration basins plays a role in spreading Legionella as described in multiple articles (Olsen et al. 2010; Loenenbach et al. 2018; Caicedo et al. 2019) and therefore included as a risk criterium. Aerosols formed through aeration allow Legionella bacteria to spread over a distance of more than 3 km (Reukers et al. 2018). Unfortunately, available literature did not yield sufficient information to differentiate the degree of risk of Legionella emission through the use of different types of aeration such as surface aeration or bubble diffusers.

Based on the four identified risk criteria, a risk matrix was developed for assessing the risk of Legionella growth and emission from WWTPs (Table 1). In this matrix, four risk categories were distinguished:

  • High risk: High to very high Legionella concentrations in aeration tanks (≥106 CFU/L) and effluent (≥104 CFU/L) can be expected, as shown in the case studies. This may result in a high risk of exposure to Legionella bacteria if aerosols are emitted from the wastewater or (discharged) effluent.

  • Moderate risk: (Temporary) Legionella growth to high concentrations is possible depending on the conditions. There is a risk of exposure to Legionella bacteria if aerosols are formed and emitted from wastewater or effluent.

  • Low risk: Legionella may be present, but a high concentration (≥106 CFU/L) is not expected under these conditions. Incidentally, the concentration of Legionella in the process water might be increased, due to influent water with high concentrations of Legionella. Possible risk of exposure if aerosols are emitted from wastewater or effluent.

  • Very low risk: Legionella is not likely to be present or is present at a very low concentration. Very low risk of exposure if aerosols are emitted from the wastewater or effluent.

Risk assessment for Legionella growth and emission to air and surface waters from WWTPs

To assess the number of WWTPs that potentially pose a risk for Legionella growth and emission to air and surface waters, an overview of existing WWTPs and their characteristics was needed. In November 2018, the Association of environmental agencies in the Netherlands (Omgevingsdienst NL (ODNL)) asked all 29 regional environmental agencies (ODs) to provide an overview of all iWWTPs in their region. Based on a questionnaire, additional information was gathered about the WWTPs. The Foundation for Applied Water Research (STOWA) made an inventory of all communal WWTP (cWWTPs) managed by the Dutch Water boards.

Based on the information received, the risk matrix was used to classify the WWTPs into four risk categories for Legionella growth and emission to air and discharge on surface waters from WWTPs: high, moderate, low, and very low risk. These risk levels do not provide information on the risk of infection or illness caused by Legionella.

Detection of Legionella

Sampling locations and sampling procedure

To verify the presence of Legionella in WWTPs with moderate to high risk of Legionella growth and emission, these WWTPs were sampled. Water samples were taken from the selected WWTPs in June and July 2019. Samples were taken at one time, so-called grab samples, according to the procedures described in ISO 19458:2006, if possible directly from the aeration tank or using a tap (ISO 2006). Water temperature (PT100 thermometer, Hanna Instruments) was measured on-site, in all samples. After sampling, samples were directly placed on melting ice or cooling-elements, and transported to the laboratory for microbiological analysis within 24 h after sampling.

Microbiological analysis

The water samples (500 mL) were concentrated using membrane filtration. Filtration was done by vacuum filtration (550 bar) with the aid of a vacuum controller (Innotech Europe BV; Moergestel; NL). The scraping technique, as described in ISO 11731: 2017 annex E, was used for the removal of the organisms from the membrane (ISO 2017). Residues were resuspended in 1 mL of sterile water. Due to the composition, not all samples could be concentrated. When this was the case, direct material was used. Of the suspension or direct material, 100 μL was inoculated without dilution and after a 10-fold and 100-fold dilution on three different agar plates at 35 °C, with increased humidity. The three agar plates used were (i) buffered charcoal yeast extract (BCYE) supplemented with α-ketoglutarate and L-cysteine (BCYE-α L-cysteine), (ii) the antibiotics polymyxin B, cefazolin, and pimaricin (BCYE AB); and (iii) the antibiotics polymyxin B, anisomysin, and vanomycin (MWY) (Thermo Fisher Scientific, Cheshire, UK). To reduce the growth of other microorganisms than Legionella, which can interfere with the recovery, portions of the water samples were also subjected to heat treatment and acid treatment. Heat treatment was done by adding the sample (concentrated or not concentrated) to a sterile container and placing it in a water bath at (50 ± 1) °C for (30 ± 2) min. Acid treatment was done by diluting one volume of the sample (concentrated or not concentrated) with nine volumes of the acid solution as described in ISO 11731: 2017 annex D, mixing well and leaving it for (5.0 ± 0.5) min (ISO 2017). The first examination was performed on day three of the total incubation period of 7 days using a dissection microscope. Suspected colonies were isolated and identified using MALDI-TOF. L. pneumophila strains were serotyped using commercially available kits containing antisera against L. pneumophila serogroups 1–14 according to manufacturer's protocol (Legionella latex test, Oxoid Limited, Hampshire, UK; Legionella antisera ‘Seiken’, Denka Seiken Co. Ltd, Tokyo, Japan).

Risk assessment of WWTPs

In total, 451 iWWTPs were identified by the Dutch environmental agencies (OD) as competent authority. The number of iWWTPs listed per environmental agency varied between 0 and 74 implying that not all iWWTPs were identified in some regions. Some environmental agencies only reported iWWTPs with biological treatment, which indicates there might be underreporting of the number of non-biological treatment iWWTPs. In addition to the iWWTPs, a total of 327 cWWTPs owned and managed by the Dutch Water Authorities were reported by the Foundation for Applied Water Research (STOWA). In contrast to iWWTPs, for cWWTPs, an up-to-date database was available. In total, 778 WWTPs were identified as shown in Figure 1.
Figure 1

Overview of communal (white dots) and industrial (black triangles) WWTPs in the Netherlands, based on the inventory.

Figure 1

Overview of communal (white dots) and industrial (black triangles) WWTPs in the Netherlands, based on the inventory.

Close modal

A risk assessment was done for all 778 WWTPs using our newly developed risk matrix (Table 1), based on the four risk criteria for Legionella growth and emission to air or effluent. A biological treatment process was part of all 327 cWWTPs and they belonged to the type of industries with organic/nutrient-rich wastewater. Aeration was used in all 327 cWWTPs during biological (aerobic) treatment. The temperature of the process water of 315 cWWTPs (96%) depended on the ambient temperature and varied between 8 and 20 °C and these were identified as ‘low’ risk. Twelve cWWTPs (4%) (partly) operated between 30 and 38 °C for optimal operation in the conversion of ammonium and nitrite into nitrogen gas using Anammox bacteria. These 12 cWWTPs were classified as ‘high’ risk (Table 2).

Table 2

Overview of the number of WWTPs in the Netherlands with the risk of Legionella growth and emission to air or surface waters based on the reported characteristics in the inventory

Risk of Legionella growth and emission to air and/or surface watersNumber of WWTPs
CommunalIndustrial
High 12 18 
Moderate to high 63 
Low 315 45 
Very low 232 
Unknown: missing information or no case studies available 93 
Risk of Legionella growth and emission to air and/or surface watersNumber of WWTPs
CommunalIndustrial
High 12 18 
Moderate to high 63 
Low 315 45 
Very low 232 
Unknown: missing information or no case studies available 93 

Preventive measures to prevent the emission of Legionella were not taken into account.

For iWWTPs, 219 out of 451 (49%) had a biological treatment process. The risk of the 232 non-biological iWWTPs was categorized as ‘very low’. There were 90 (41%) biological iWWTPs that received wastewater from other industries. Insufficient information about the composition of the influent was available and no case study for these industries was described. Therefore, no risk could be estimated and these 90 iWWTPs were classified as ‘unknown’ risk. More than half of the biological iWWTPs (59%, n = 129) belonged to the selected industries with organic/nutrient-rich wastewater: food industry (n = 101), petrochemical companies (n = 10), wood and paper industry (n = 9), rendering companies (n = 1), and (partly) communal wastewater (n = 8). For three out of these 129 iWWTPs, the risk for Legionella growth and emission could not be assessed (unknown) as the temperature of the process water was not reported. The risk for Legionella growth and emission was categorized as ‘low’ for 45 out of these 129 iWWTPs with a temperature of the process water not in the range of 25–45 °C. For 81 out of these 129 iWWTPs, the temperature of the process water was listed between 25 and 45 °C. For 18 iWWTPs, the temperature of the process water range was reported to be completely within the range of 30–38 °C, and therefore, the risk for Legionella growth and emission was categorized as ‘high’. For the remaining 63 iWWTPs with a biological treatment process, the water temperature was reported as between 25 and 45 °C or only indicated as elevated temperature. Therefore, the risk was estimated as ‘moderate to high’ (Table 2).

For some locations, the requested information was not specified, incomplete or not correct. At some locations, for example, the reported temperature of the process from the inventory differed from the measured water temperature during sampling. If data is not correctly reported, this might have a negative effect on the risk assessment and WWTPs with a ‘moderate’ to ‘high’ risk might be assessed lower. Compared to cWWTPs for iWWTPs, it was more complicated to collect this information as a central registration of iWWTPs does not exist. To provide more information on the role of Legionella growth and emission from WWTPs and to assess the risk, an accurate overview of all WWTPs and their characteristics should be made available and kept up-to-date.

Detection of Legionella

Together with STOWA, the Dutch Water Authorities responsible for all cWWTPs developed voluntarily their own sampling strategy for high risk cWWTPs and were not included in this study. The Legionella detection focused on iWWTP classified as ‘moderate to high’ or ‘high’ risk (Table 2). In total, 81 iWWTPs were selected for sampling and analysis of which 63 iWWTPs with ‘moderate to high’ risk and 18 iWWTPs with ‘high’ risk. At the request of the environmental agencies, 11 iWWTPs were added to the final selection ending up with 92 iWWTPs. Finally, 85 of the 92 iWWTPs were sampled and analyzed for the detection of Legionella (Table 3). At seven iWWTPs, no samples could be taken due to maintenance, miscommunication, or problems during sampling.

Table 3

Overview of the results of Legionella detection in iWWTPs categorized on the risk level

Risk levelMeasured temperature of process water (°C)Number iWWTPs sampled (Legionella positive iWWTP) per type of industry
Food industryPetrochemical companyWood and paper industryRendering companyNon-specific WWTPSludge and manureTotal
Low <25 9 (0) 1 (0)     10 (0) 
Moderate 25–29 13 (1)
1: L.p sg5 
3 (1)
1: L.spp 
2 (2)
1: L.p 7–14
2: L.p 7–14 
 3 (1)
1: L.p sg1 
 21 (5) 
High 30–38 32 (3)
1: L.p sg1 and L.p sg2
2: L.p sg3 and L.p sg5
3: L.p sg2 
5 (2)
1: L.p sg1 and L.p sg5
2: L.p sg5 
6 (2)
1: L.p sg1
2: L.p sg6 
1 (1)
1: L.p sg1 
3 (0)  47 (8) 
Moderate 39–45 3 (0)      3 (0) 
Unknown 30–38     1 (0) 2 (2)
1:.L. bozemanii
2: L.p sg3 and L.p sg6 
3 (2) 
Total  57 (4) 9 (3) 8 (4) 1 (1) 8 (1) 2 (2) 85 (15) 
Risk levelMeasured temperature of process water (°C)Number iWWTPs sampled (Legionella positive iWWTP) per type of industry
Food industryPetrochemical companyWood and paper industryRendering companyNon-specific WWTPSludge and manureTotal
Low <25 9 (0) 1 (0)     10 (0) 
Moderate 25–29 13 (1)
1: L.p sg5 
3 (1)
1: L.spp 
2 (2)
1: L.p 7–14
2: L.p 7–14 
 3 (1)
1: L.p sg1 
 21 (5) 
High 30–38 32 (3)
1: L.p sg1 and L.p sg2
2: L.p sg3 and L.p sg5
3: L.p sg2 
5 (2)
1: L.p sg1 and L.p sg5
2: L.p sg5 
6 (2)
1: L.p sg1
2: L.p sg6 
1 (1)
1: L.p sg1 
3 (0)  47 (8) 
Moderate 39–45 3 (0)      3 (0) 
Unknown 30–38     1 (0) 2 (2)
1:.L. bozemanii
2: L.p sg3 and L.p sg6 
3 (2) 
Total  57 (4) 9 (3) 8 (4) 1 (1) 8 (1) 2 (2) 85 (15) 

The number of sampled iWWTPs is given per industry and the number of Legionella positive iWWTPs is shown between brackets. For the Legionella positive iWWTPs, the species including serogroup is given per positive iWWTP. L.p = Legionella pneumophila and sg = serogroup.

During sampling, the water temperature sometimes differed from the reported information at the inventory. The water temperature of eight iWWTPs during sampling was below 25 °C compared with the reported temperature range of 25–40 °C, resulting in a lower risk than expected. One iWWTP that was added at the request of the environmental agency, had a temperature of 33 °C, but had been reported as below 25 °C in the inventory and was therefore originally not included in the selection of high risk iWWTPs. iWWTPs were categorized based on the registered temperature of the water during sampling and was used for assessing the risk level (Table 3).

In this study, we found Legionella spp. 15 iWWTPs (18%). At 13 locations (15%), L. pneumophila was detected and at two locations Legionella non-pneumophila was found of which at one location it was determined as L. bozemanii (Table 3). Lund et al. (2014) found comparable results: 21 out of 130 analyses (16%) from iWWTPs samples were positive for Legionella spp. and 12 (9%) were positive for L. pneumophila (Lund et al. 2014). The concentrations for Legionella varied between 1 × 105 and 3 × 108 CFU/L which was similar to concentrations found in other studies (Olsen et al. 2010; Loenenbach et al. 2018).

Serotyping of L. pneumophila showed a diversity of serogroups and in five iWWTPs serogroup 1 was found (Table 3). L pneumophila serogroup 1 is the causative agent for most of the patients with diagnosed LD in the Netherlands (Reukers et al. 2019). Sequence typing of L. pneumophila serogroup 1 gave the following STs: ST47, ST474, ST1095, and ST1646. One iWWTP sample contained both ST1095 and ST1646. Notable, one L. pneumophila serogroup 1 isolate was ST-type 47. This virulent strain is found in 41% of the clinical isolates of Dutch non-travel-associated patients (Den Boer et al. 2015). Although this ST-type has also been detected in spa pools and soil (Schalk et al. 2014), it was not found in other water samples during 10 years of systematic sampling of potential sources (Den Boer et al. 2015).

The positive Legionella results were directly communicated to the responsible OD for follow-up with the owner of the iWWTP and investigated if additional control measures are required to protect public health. When Legionella is detected in the wastewater, it is recommended to take action to prevent emission to air or discharge on surface waters and, if possible, reduce the Legionella concentration. The first step is treating biological systems for selectively reducing Legionella without interfering with the biological process in the system, such as adding an ‘Expanded Granular Sludge Blanket’ reactor (Nogueira et al. 2016). If reduction of Legionella is not possible, then minimize the emission of Legionella from the WWTP. To reduce emission from WWTPs to air, the aeration basins could be covered with a tarpaulin or floating balls although the effect depends on how well the surface is covered (Lodder et al. 2019). When the air was extracted from closed aeration basins and subsequently filtered and disinfected with UV radiation the number of Legionella bacteria in the air decreased dramatically (Lodder et al. 2019). An additional treatment of effluent water, such as (membrane) filtration or UV treatment, could be applied to improve the water quality of the receiving surface waters (Collivignarelli et al. 2018).

ISO 11731: 2017 is often used for determining the number of Legionella bacteria in water, but when applied to wastewater, this method can give a wide variation of results (ISO 2017). Due to high concentration of other (interfering) microorganisms and the high detection limit for Legionella (approximately 10,000 CFU/L), it is rather difficult to detect Legionella bacteria in highly polluted wastewater. The sample pre-treatment conditions for wastewater are harsh and can affect Legionella’s cultivability (Whiley & Taylor 2016). Furthermore, culture-based methods such as ISO 11731 are not able to detect Legionella in the viable but non-culturable (VBNC) state (Whiley & Taylor 2016, Caicedo et al. 2019). This leads to an underestimation of the real Legionella concentration in the sample (Whiley & Taylor 2016). Legionella bacteria in the VBNC state can grow under the correct conditions. If Legionella cannot be detected in a wastewater sample with the used method, this means that no viable Legionella or less than 10,000 CFU/L Legionella bacteria are present in the sample. The iWWTPs in our study were sampled only once by taking a grab sample in the months of June and July. It is unknown how many WWTPs false negative results were obtained because of the high detection limit or because of other factors like the time period when samples were taken. The consequence of false negative results can be that no control measures are taken or control measures might appear more effective than they really are (Caicedo et al. 2019). Using molecular techniques, L. pneumophila and Legionella spp. are more frequently detected as compared with culture methods (Medema et al. 2004; Lund et al. 2014). Lund et al. (2014) investigated various industrial and communal WWTPs for the presence of Legionella and found that most samples (99%) were Legionella spp. positive by PCR, whereas Legionella could be detected less frequently (16%) using culture methods (Lund et al. 2014). We found similar results in our study (data not shown). The benefits of PCR are rapidly available results and the detection of Legionella bacteria in the VBNC state. The PCR method does not differentiate between alive or dead Legionella bacteria, and therefore, no information is gathered on the viable Legionella bacteria present (Caicedo et al. 2019). However, based on the limitations of the culture method for wastewater and the high detection rates with molecular techniques, the number of Legionella positive iWWTPs in this study is expected to be underestimated.

The majority of sampled iWWTPs (67%) processed wastewater from food industries whereas only one iWWTP from a rendering company was sampled. In all different types of industry, at least one iWWTP tested positive for Legionella varying between 7 and 100% Legionella positive iWWTPs per industry, which is in line with other published studies (Blatny et al. 2008; Kusnetsov et al. 2010; Loenenbach et al. 2018; Caicedo et al. 2019). In addition to industries with organic/nutrient-rich process water as described in the literature, other industries may also produce nutrient-rich wastewater, which promotes Legionella growth (Caicedo et al. 2019). In this study, two industries treating manure and sludge were Legionella positive but were not included as high risk industries. Furthermore, industries without nutrient-rich wastewater may sometimes receive nutrient-rich wastewater from other companies for processing in their WWTP. This may be the case for both cWWTPs and iWWTPs. Therefore, it is recommended to assess the risk for other industries, especially if nutrient-rich water is expected. If other industries should be included the risk matrix needs to be adapted.

The process water of the 15 Legionella positive samples had a temperature between 25 and 29 °C (n = 5) or 30 and 38 °C (n = 10). Similar to other studies, all Legionella positive samples were derived from iWWTP with process water temperatures between 25 and 38 °C (Blatny et al. 2008; Kusnetsov et al. 2010; Maisa et al. 2015; Loenenbach et al. 2018). This indicates that the selected range is an important criterion with increased risk. The percentages of Legionella positive iWWTPs with water between 25–29 °C and 30–38 °C were respectively 24 and 17%. Ten iWWTPs with temperatures of the process water below 25 °C and three iWWTPs with a temperature of the process water above 39 °C tested negative for the detection of Legionella spp. (Table 3). Based on the findings, we would suggest to divide the process water temperature below and above 25 °C. Furthermore, if WWTPs with a water temperature below 25 °C receive wastewater with high Legionella concentrations this may also result in high concentrations in the aeration tanks, although growth will be limited. Legionella growth does not only depend on the water temperature. There may also be circumstances where the temperature is stratified in the basin or changes temporarily, so the concentration could increase or decrease over time (Caicedo et al. 2016).

The risk matrix for assessing the risk of Legionella growth and emission from WWTPs was based on available information in the literature. New data might lead to an addition to or change in risk criteria.

For WWTPs with ‘moderate’ to ‘high’ risk of Legionella growth and emission, it is needed to check the existing measures in place. Existing control measures might contribute to a lower risk of Legionella growth or reduce the concentration of Legionella are a prolonged anaerobic step or treating effluent with an extra purification step, e.g. UV or additive biocides (Nogueira et al. 2016; Collivignarelli et al. 2018). Control measures to reduce the emission of Legionella include covering the aeration tank with concrete, tarpaulin or balls, and use of pure oxygen instead of normal aeration (Caicedo et al. 2019). These control measures aim to limit or prevent the emission of Legionella. However, when the high concentration of Legionella in the WWTP remains and in case of a hazardous event, it may still spread to the environment. When treated effluent or surface waters receiving treated effluent containing Legionella is used in cooling towers or for other activities, aerosols with Legionella can be spread (Nogueira et al. 2016). Due to water scarcity re-use of treated wastewater becomes an important alternative water source. For aerosol-forming applications such as irrigation and cooling towers, the presence of Legionella in treated wastewater might pose a health risk (Caicedo et al. 2019). Regulation of Legionella in effluent water used for application with a risk of aerosolization is needed to protect human health, such as the requirement of a maximum of 1,000 Legionella CFU/l in the EU regulation (EU 2022).

For high risk WWTPs, it is recommended that both operational monitoring of the WWTP is initiated and a management plan is developed. More research on control measures is needed to identify how Legionella growth and emission could be controlled. For existing WWTPs, it is recommended to adjust the treatment process so that Legionella growth is prevented or at least controlled as much as possible similar to Legionella prevention in wet cooling towers. If Legionella is present in high numbers it is recommended to reduce the concentration and avoid emission of Legionella, especially via air. A sustainable solution for new WWTPs is to design a process that limits the growth and/or emission of Legionella. To support owners of WWTPs to identify, interpret, and control Legionella risks, a guidance document was drafted using the findings of this study (Oesterholt & Hollebekkers 2022).

To improve the risk assessment for the emission of Legionella to air or surface water from WWTPs, existing measures and their local application to prevent the emission of aerosols should be taken into account.

Biological WWTPs are possible sources of LD and need to be considered during source investigation. In this paper, a risk assessment methodology was drafted to identify WWTPs at risk of Legionella growth and emission. The risk matrix is based on information about the WWTPs that is relatively easy to identify, and therefore, this approach is likely applicable for many countries to identify possible sources for Legionella emission from WWTPs. To provide more information on the role of Legionella growth and emission from WWTPs and to assess the risk, an accurate overview of all WWTPs and their characteristics should be made available and kept up-to-date.

In this study, 18% of the iWWTPs with moderate to high risk for growth and emission of Legionella were Legionella spp. positive, and two iWWTPs with unknown risks were positive. The true proportion of Legionella positive WWTPs may be even higher, as the culture method does not detect low concentrations of Legionella in wastewater. Based on the risk assessment of WWTPs and Legionella spp. detected with culture methods revising the risk matrix based on new scientific evidence and information on Legionella outbreaks is needed. Additional research is needed to further improve the risk matrix. Nevertheless, the current risk matrix can be used to develop a risk-based monitoring program starting at WWTPs with the highest risk of Legionella emission.

For WWTPs with a high risk, it is recommended that both operational monitoring of the WWTP is initiated and a sampling plan is drawn up and implemented, a so-called management plan. For assessing the risks for WWTPs, it is crucial that the location of such installations is known, therefore registration of WWTPs is recommended. For WWTPs still to be built or when new treatment technologies are installed, it is recommended to guarantee that Legionella growth is prevented or at least controlled as much as possible.

This study was funded by the Dutch Ministry of Infrastructure and Water Management and the Association of Environmental Agencies in the Netherlands (ODNL). The authors are grateful to environmental agencies for both carrying out the inventory and contacting the iWWTPs to sample, especially Diany Stoel and Mark van Rijn (OD Brabant Noord) for their coordinating with all environmental agencies. The authors like to thank Imke Leenen and Cora Uijterlinde (STOWA) for organizing the inventory at the cWWTPs. We thank Omegam for sampling the selected iWWTPs. Finally, the authors would like to thank Robin van Leerdam, Melissa Stunnenberg and Ingmar Janse (RIVM) and Femke van den Berg for reviewing the manuscript.

All relevant data are included in the paper or its Supplementary Information.

The authors declare there is no conflict.

Allestam
G.
,
de Jong
B.
&
Langmark
J.
2006
Chapter 119: Biological treatment of industrial wastewater: a possible source of Legionella infection
. In: Cianciotto, N., Kwaik, Y., Edelstein, P., Fields, B., Geary, D., Harrison, T., Joseph, C., Ratcliff, R., Stout, J. & Swanson, M. (Eds.)
Legionella: State of the Art 30 Years After Its Recognition
.
ASM Press
, pp.
493
496
.
Bartels
A. A.
,
van Leerdam
R. C.
,
Lodder
W. J.
,
Vermeulen
L. C.
&
van den Berg
H. H. J. L.
2019
Inventarisatie van legionellarisico's bij afvalwaterzuiveringsinstallaties. RIVM Report 2019-0061
.
Blatny
J. M.
,
Reif
B. A.
,
Skogan
G.
,
Andreassen
O.
,
Hoiby
E. A.
,
Ask
E.
,
Waagen
V.
,
Aanonsen
D.
,
Aaberge
I. S.
&
Caugant
D. A.
2008
Tracking airborne Legionella and Legionella pneumophila at a biological treatment plant
.
Environmental Science and Technology
42
,
7360
7367
.
Caicedo
C.
,
Beutel
S.
,
Scheper
T.
,
Rosenwinkel
K. H.
&
Nogueira
R.
2016
Occurrence of Legionella in wastewater treatment plants linked to wastewater characteristics
.
Environmental Science and Pollution Research International
23
,
16873
16881
.
Caicedo
C.
,
Rosenwinkel
K. H.
,
Exner
M.
,
Verstraete
W.
,
Suchenwirth
R.
,
Hartemann
P.
&
Nogueira
R.
2019
Legionella occurrence in municipal and industrial wastewater treatment plants and risks of reclaimed wastewater reuse: review
.
Water Research
149
,
21
34
.
Collivignarelli
M. C.
,
Abbà
A.
,
Benigna
I.
,
Sorlini
S.
&
Torretta
V.
2018
Overview of the main disinfection processes for wastewater and drinking water treatment plants
.
Sustainability
10
,
86
.
Den Boer
J. W.
,
Euser
S. M.
,
Brandsema
P.
,
Reijnen
L.
&
Bruin
J. P.
2015
Results from the National Legionella Outbreak Detection Program, The Netherlands, 2002–2012
.
Emerging Infectious Diseases
21
,
1167
1173
.
EU
2022
Regulation (EU) 2020/741 of the Parliament and of the Council on Minimum Requirement for Water Reuse
.
Official Journal of the European Union
,
Brussels
.
Euser
S. M.
,
Bruin
J. P.
,
Brandsema
P.
,
Reijnen
L.
,
Boers
S. A.
&
Den Boer
J. W.
2013
Legionella prevention in the Netherlands: an evaluation using genotype distribution
.
European Journal of Clinical Microbiology & Infectious Diseases
32
,
1017
1022
.
Gregersen
P.
,
Grunnet
K.
,
Uldum
S. A.
,
Andersen
B. H.
&
Madsen
H.
1999
Pontiac fever at a sewage treatment plant in the food industry
.
Scandinavian Journal of Work, Environment & Health
25
,
291
295
.
International Organization for Standardization (ISO)
2006
ISO 19458: 2006 Water Quality – Sampling for Microbiological Analysis
.
Switzerland. ISO copyright office.
International Organization for Standardization (ISO)
2017
ISO 11731:2017 Water Quality – Enumeration of Legionella
.
Switzerland. ISO copyright office.
Isozumi
R.
,
Ito
Y.
,
Ito
I.
,
Osawa
M.
,
Hirai
T.
,
Takakura
S.
,
Iinuma
Y.
,
Ichiyama
S.
,
Tateda
K.
,
Yamaguchi
K.
&
Mishima
M.
2005
An outbreak of Legionella pneumonia originating from a cooling tower
.
Scandinavian Journal of Infectious Diseases
37
,
709
711
.
Kusnetsov
J.
,
Neuvonen
L. K.
,
Korpio
T.
,
Uldum
S. A.
,
Mentula
S.
,
Putus
T.
,
Tran Minh
N. N.
&
Martimo
K. P.
2010
Two Legionnaires' disease cases associated with industrial wastewater treatment plants: a case report
.
BMC Infectious Diseases
10
,
343
.
Lodder
W. J.
,
Van den Berg
H. H. J. L.
,
Van Leerdam
R. C.
&
De Roda Husman
A. M.
2019
Potentiële maatregelen tegen verspreiding van Legionella uit afvalwaterzuiveringsinstallaties RIVM Report 2019-0194
.
Loenenbach
A. D.
,
Beulens
C.
,
Euser
S. M.
,
van Leuken
J. P. G.
,
Bom
B.
,
van der Hoek
W.
,
de Roda Husman
A. M.
,
Ruijs
W. L. M.
,
Bartels
A. A.
,
Rietveld
A.
,
den Boer
J. W.
&
Brandsema
P. S.
2018
Two community clusters of Legionnaires’ disease directly linked to a biologic wastewater treatment plant, the Netherlands
.
Emerging Infectious Diseases
24
,
1914
1918
.
Lund
V.
,
Fonahn
W.
,
Pettersen
J. E.
,
Caugant
D. A.
,
Ask
E.
&
Nysaeter
A.
2014
Detection of Legionella by cultivation and quantitative real-time polymerase chain reaction in biological wastewater treatment plants in Norway
.
Journal of Water and Health
12
,
543
554
.
Maisa
A.
,
Brockmann
A.
,
Renken
F.
,
Luck
C.
,
Pleischl
S.
,
Exner
M.
,
Daniels-Haardt
I.
&
Jurke
A.
2015
Epidemiological investigation and case-control study: a Legionnaires’ disease outbreak associated with cooling towers in Warstein, Germany, August-September 2013
.
Eurosurveillance
20
(46), 30064
.
Medema
G. J.
,
Wullings
B.
,
Roeleveld
P.
&
Van der Kooij
D.
2004
Risk assessment of Legionella and enteric pathogens in sewage treatment works
.
Water Science & Technology Water Supply
4
,
125
132
.
Nguyen
T. M.
,
Ilef
D.
,
Jarraud
S.
,
Rouil
L.
,
Campese
C.
,
Che
D.
,
Haeghebaert
S.
,
Ganiayre
F.
,
Marcel
F.
,
Etienne
J.
&
Desenclos
J. C.
2006
A community-wide outbreak of legionnaires disease linked to industrial cooling towers–how far can contaminated aerosols spread?
Journal of Infectious Diseases
193
,
102
111
.
Nogueira
R.
,
Utecht
K. U.
,
Exner
M.
,
Verstraete
W.
&
Rosenwinkel
K. H.
2016
Strategies for the reduction of Legionella in biological treatment systems
.
Water Science and Technology
74
,
816
823
.
Nygård
K.
,
Werner-Johansen
Ø.
,
Rønsen
S.
,
Caugant
D. A.
,
Simonsen
Ø.
,
Kanestrøm
A.
,
Ask
E.
,
Ringstad
J.
,
Ødegård
R.
,
Jensen
T.
,
Krogh
T.
,
Høiby
E. A.
,
Ragnhildstveit
E.
,
Aaberge
I. S.
&
Aavitsland
P.
2008
An outbreak of Legionnaires disease caused by long-distance spread from an industrial air scrubber in Sarpsborg, Norway
.
Clinical Infectious Diseases
46
,
61
69
.
Oesterholt
F.
&
Hollebekkers
F.
2022
Handreiking legionellapreventie in biologische afvalwaterzuiveringsinstallaties (Nieuwegein, KWR)
.
Olsen
J. S.
,
Aarskaug
T.
,
Thrane
I.
,
Pourcel
C.
,
Ask
E.
,
Johansen
G.
,
Waagen
V.
&
Blatny
J. M.
2010
Alternative routes for dissemination of Legionella pneumophila causing three outbreaks in Norway
.
Environmental Science and Technology
44
,
8712
8717
.
Reukers
D. F. M.
,
van Asten
L.
,
Brandsema
P. S.
,
Dijkstra
F.
,
Donker
G. A.
,
van Gageldonk-Lafeber
A. B.
,
Hooiveld
M.
,
de Lange
M. M. A.
,
Marbus
S.
,
Teirlinck
A. C.
,
Meijer
A.
&
van der Hoek
W.
2018
Annual Report Surveillance of Influenza and Other Respiratory Infections: Winter 2017/2018 = Surveillance van griep en andere luchtweginfecties: Winter 2017/2018. RIVM Rapport
.
Reukers
D. F. M.
,
van Asten
L.
,
Brandsema
P. S.
,
Dijkstra
F.
,
Donker
G. A.
,
van Gageldonk-Lafeber
A. B.
,
Hooiveld
M.
,
de Lange
M. M. A.
,
Marbus
S.
,
Teirlinck
A. C.
,
Meijer
A.
&
van der Hoek
W.
2019
Annual Report Surveillance of Influenza and Other Respiratory Infections in the Netherlands: Winter 2018/2019. RIVM Report
.
Schalk
J. A.
,
Docters van Leeuwen
A. E.
,
Lodder
W. J.
,
de Man
H.
,
Euser
S.
,
den Boer
J. W.
&
de Roda Husman
A. M.
2012
Isolation of Legionella pneumophila from pluvial floods by amoebal coculture
.
Applied and Environmental Microbiology
78
,
4519
4521
.
Schalk
J. A.
,
Euser
S. M.
,
van Heijnsbergen
E.
,
Bruin
J. P.
,
den Boer
J. W.
&
de Roda Husman
A. M.
2014
Soil as a source of Legionella pneumophila sequence type 47
.
International Journal of Infectious Diseases
27
,
18
19
.
Steinert
M.
,
Hentschel
U.
&
Hacker
J.
2002
Legionella pneumophila: an aquatic microbe goes astray
.
FEMS Microbiology Reviews
26
,
149
162
.
https://doi.org/10.1016/S0168-6445(02)00093-1
.
van Heijnsbergen
E.
,
Schalk
J. A.
,
Euser
S. M.
,
Brandsema
P. S.
,
den Boer
J. W.
&
de Roda Husman
A. M.
2015
Confirmed and potential sources of Legionella reviewed
.
Environmental Science and Technology
49
,
4797
4815
.
Vermeulen
L. C.
,
Brandsema
P. S.
,
van de Kassteele
J.
,
Bom
B. C. J.
,
Sterk
H. A. M.
,
Sauter
F. J.
,
van den Berg
H. H. J. L.
&
de Roda Husman
A. M.
2021
Atmospheric dispersion and transmission of Legionella from wastewater treatment plants: a 6-year case-control study
.
International Journal of Hygiene and Environmental Health
237
,
113811
.
Wadowsky
R. M.
,
Wolford
R.
,
McNamara
A. M.
&
Yee
R. B.
1985
Effect of temperature, pH, and oxygen level on the multiplication of naturally occurring Legionella pneumophila in potable water
.
Applied and Environmental Microbiology
49
,
1197
1205
.
Whiley
H.
&
Taylor
M.
2016
Legionella detection by culture and qPCR: comparing apples and oranges
.
Critical Reviews in Microbiology
42
,
65
74
.
This is an Open Access article distributed under the terms of the Creative Commons Attribution Licence (CC BY-NC-ND 4.0), which permits copying and redistribution for non-commercial purposes with no derivatives, provided the original work is properly cited (http://creativecommons.org/licenses/by-nc-nd/4.0/).