Skip to Main Content
Table 2

Characteristics of wastewater and reclaimed water compared to Kuwait's standards

ParameterUnitInflow to WWTPInflow to water reclamation plantRO effluent for reuseIrrigation water standardsDrinking water standards
pH – 6.5–8 6.5–7.5 6–8 6.5–8 6.8–7.5 
Conductivity µs/cm 1,200–3,000 1,100–2,200 – 1,500 515 
TSS mg/L 100–500 <10 <1 15 – 
VSS mg/L 70–350 <7.0 <1 – – 
COD mg/L 250–750 <40 15 100 – 
BOD5 mg/L 100–400 <10 <1 20 – 
Grease and oil mg/L 10–50 NIL < 0.05 – 
TDS mg/L 700–1,800 800–1,500 < 100 – 400 
Chloride mg/L 200–400 200–400 – – 103 
Ammonia mg/L 15–50 1–5 <1 15 – 
Nitrite mg/L 0.04–0.7 0.1–1.5 <1 – – 
Heterotrophic plate counts cfu/100mL 2.40 × 109 103 – 
Total coliforms cfu/100 mL 3.20 × 108 400 400 
Faecal coliforms cfu/100 mL 4.10 × 107 0–10 20 
Salmonella cfu/100 mL 4.50 × 106 – 
Streptococci cfu/100 mL 1.40 × 107 – 
Fungi cfu/100 mL 2.10 × 105 2–100 – 
ParameterUnitInflow to WWTPInflow to water reclamation plantRO effluent for reuseIrrigation water standardsDrinking water standards
pH – 6.5–8 6.5–7.5 6–8 6.5–8 6.8–7.5 
Conductivity µs/cm 1,200–3,000 1,100–2,200 – 1,500 515 
TSS mg/L 100–500 <10 <1 15 – 
VSS mg/L 70–350 <7.0 <1 – – 
COD mg/L 250–750 <40 15 100 – 
BOD5 mg/L 100–400 <10 <1 20 – 
Grease and oil mg/L 10–50 NIL < 0.05 – 
TDS mg/L 700–1,800 800–1,500 < 100 – 400 
Chloride mg/L 200–400 200–400 – – 103 
Ammonia mg/L 15–50 1–5 <1 15 – 
Nitrite mg/L 0.04–0.7 0.1–1.5 <1 – – 
Heterotrophic plate counts cfu/100mL 2.40 × 109 103 – 
Total coliforms cfu/100 mL 3.20 × 108 400 400 
Faecal coliforms cfu/100 mL 4.10 × 107 0–10 20 
Salmonella cfu/100 mL 4.50 × 106 – 
Streptococci cfu/100 mL 1.40 × 107 – 
Fungi cfu/100 mL 2.10 × 105 2–100 – 

VSS, volatile suspended solids.

Close Modal

or Create an Account

Close Modal
Close Modal