Measured water quality parameters, volume collected for N. fowleri testing, and N. fowleri detections for water samples collected from DeSoto parish system before chlorine conversion, September 2013
Site ID . | Location . | Total chlorine (mg/L) . | Temperature (°C) . | Volume collected (L) . | N. fowleri culture . |
---|---|---|---|---|---|
D1 | Point of collection sample tap | 0.10 | 29 | 737 | + |
D2 | Flush hydrant | 0.05 | 28 | 775 | + |
D3 | Flush hydrant | 0.05 | 30 | 641 | + |
D4 | Flush hydrant | 0.08 | 34 | 231 | + |
D5 | Point of collection sample tap | 0.40 | 26 | 246 | – |
D6 | Fire hydrant | 0.20 | 26 | 206 | – |
D7 | Fire hydrant | 0.44 | 32 | 418 | + |
D8 | Flush hydrant | 0.15 | 31 | 598 | + |
D9 | Point of collection sample tap | 0.10 | 23 | 105 | – |
D10 | Fire hydrant | 0.09 | 30 | 565 | – |
Site ID . | Location . | Total chlorine (mg/L) . | Temperature (°C) . | Volume collected (L) . | N. fowleri culture . |
---|---|---|---|---|---|
D1 | Point of collection sample tap | 0.10 | 29 | 737 | + |
D2 | Flush hydrant | 0.05 | 28 | 775 | + |
D3 | Flush hydrant | 0.05 | 30 | 641 | + |
D4 | Flush hydrant | 0.08 | 34 | 231 | + |
D5 | Point of collection sample tap | 0.40 | 26 | 246 | – |
D6 | Fire hydrant | 0.20 | 26 | 206 | – |
D7 | Fire hydrant | 0.44 | 32 | 418 | + |
D8 | Flush hydrant | 0.15 | 31 | 598 | + |
D9 | Point of collection sample tap | 0.10 | 23 | 105 | – |
D10 | Fire hydrant | 0.09 | 30 | 565 | – |