Skip to Main Content
Table 2

Corrosion rate of carbon steel coupon with and without CMP

TestSerial number of couponWeightless value (g)Corrosion rate (mm/a)Average corrosion rate (mm/a)
Corrosion coupon experiment without CMP 0.7160 1.0809 1.0979 
0.7635 1.1526 
0.7023 1.0602 
Corrosion coupon experiment with CMP 0.0014 0.0021 0.0034 
0.0028 0.0042 
0.0026 0.0039 
Circulating cooling water experiment with CMP 0.1264 0.0636 0.0654 
0.1338 0.0673 
0.1298 0.0653 
TestSerial number of couponWeightless value (g)Corrosion rate (mm/a)Average corrosion rate (mm/a)
Corrosion coupon experiment without CMP 0.7160 1.0809 1.0979 
0.7635 1.1526 
0.7023 1.0602 
Corrosion coupon experiment with CMP 0.0014 0.0021 0.0034 
0.0028 0.0042 
0.0026 0.0039 
Circulating cooling water experiment with CMP 0.1264 0.0636 0.0654 
0.1338 0.0673 
0.1298 0.0653 