Skip to Main Content
Table 6

The designed parameters of the pressurized-pot microfiltration system

NumberParameterDesigned value
Net rate of water production ≥111,200 m3/d (4–30 °C) 
Number of series 
Number of pressurized-pot set 10 
Filtration rate of one filter ≥2.10 m3/h 
Filtration area of one filter ≤2.5 m2 
Diameter of filtration bores ≤6 μm 
Removal rate of particles with diameter larger than 1.5 μm >95% 
Removal rate of particles with diameter larger than 6 μm >99.9% 
SDI of produced water <5 
10 Interval between physical cleanings ≥24 h 
11 Interval between chemical cleanings About 7–15 days 
NumberParameterDesigned value
Net rate of water production ≥111,200 m3/d (4–30 °C) 
Number of series 
Number of pressurized-pot set 10 
Filtration rate of one filter ≥2.10 m3/h 
Filtration area of one filter ≤2.5 m2 
Diameter of filtration bores ≤6 μm 
Removal rate of particles with diameter larger than 1.5 μm >95% 
Removal rate of particles with diameter larger than 6 μm >99.9% 
SDI of produced water <5 
10 Interval between physical cleanings ≥24 h 
11 Interval between chemical cleanings About 7–15 days 