Conventional automatic production flow control and pump pressure control of water supply systems are robust and simple: production flow is controlled based on the level in the clear water reservoir and pump pressure is controlled on a static set-point. Recently, more advanced computer-based control methods were developed in which production flow is controlled by using a short-term water demand forecasting model and pressure is controlled by a dynamic pressure control module. To assess the differences between conventional and advanced control, we examined operational data of water treatment plantGruszczyn that supplies drinking water to a part of the city of Poznań, Poland. We compared two periods of three weeks of conventional and advanced control. The comparison showed that with advanced control the variation in the production flow was 83% lower, and the pump pressure of the clear water pumps was 29% lower. The lower pressure resulted in 20% less background leakage and the overall system's energy costs were 11.5% lower.
Skip Nav Destination
Article navigation
Research Article|
June 01 2014
Advanced control of a water supply system: a case study
M. Bakker;
M. Bakker
*
aFaculty of Civil Engineering and Geosciences, Delft University of Technology, P.O. Box 5048, 2600 GA Delft, The Netherlands
bRoyal HaskoningDHV B.V., P.O. Box 1132, 3800 BC Amersfoort, The Netherlands
*Corresponding author. E-mail: [email protected]
Search for other works by this author on:
T. Rajewicz;
T. Rajewicz
cAquanet S.A., ul. Dolna Wilda 126, 61- 492 Poznań, Poland
Search for other works by this author on:
H. Kien;
H. Kien
dOasen N.V., Postbus 122, 2800 AC Gouda, The Netherlands
Search for other works by this author on:
J. H. G. Vreeburg;
J. H. G. Vreeburg
eSub-Department of Environmental Technology, Wageningen University, P.O. Box 17, 6700 AA Wageningen, The Netherlands
fKWR Watercycle Research Institute, P.O. Box 1072, 4330 BB Nieuwegein, The Netherlands
Search for other works by this author on:
L. C. Rietveld
L. C. Rietveld
aFaculty of Civil Engineering and Geosciences, Delft University of Technology, P.O. Box 5048, 2600 GA Delft, The Netherlands
Search for other works by this author on:
Water Practice and Technology (2014) 9 (2): 264–276.
Citation
M. Bakker, T. Rajewicz, H. Kien, J. H. G. Vreeburg, L. C. Rietveld; Advanced control of a water supply system: a case study. Water Practice and Technology 1 June 2014; 9 (2): 264–276. doi: https://doi.org/10.2166/wpt.2014.030