The City of Los Angeles, Bureau of Sanitation, has implemented thermophilic anaerobic sludge digestion at the Hyperion and Terminal Island Treatment Plants (HTP and TITP). A two-stage continuous-batch process was established at HTP, while a single-stage sequencing batch process was established at TITP. This was to evaluate compliance with the Class A pathogen reduction requirements of U.S. EPA 40 CFR Part 503. A rapid increase of the digester temperature at TITP from 57.5 to 65.5°C caused an increase of the volatile fatty acid to alkalinity ratio, a decline in digester performance, and an elevated production of methyl mercaptan and hydrogen sulfide. A rapid increase of the digester temperature at HTP from 54 to 58°C caused an elevated production of methyl mercaptan, but the effect on the volatile fatty acid to alkalinity ratio and digester performance was insignificant. It is likely that these effects observed at TITP and HTP were transient responses to rapid changes in temperature.