Coal chemical industry (CCI) generally utilizes reverse osmosis (RO) for water reclamation, which generates a highly concentrated stream containing refractory organic substances and high-concentration total dissolved solids (TDS). To address this issue, the present work focuses on volume reduction of RO concentrate (ROC) produced from CCI by forward osmosis (FO). We investigated the effects of membrane orientation and draw solution (DS) concentration on FO performance. Foulant removal was tested by using chemical cleaning, physical cleaning and osmotic backwash (OB). AL-FS (active layer facing feed solution) mode outcompeted AL-DS (active layer facing draw solution) mode, achieving a flux of 26.4 LMH, 92.5% water reclamation and energy consumption of 0.050 kWh·m−3 with 4 M NaCl as DS. The FO process was able to reject >98% SO42−, Mg2+and Ca2+, 92–98% Si and 33–55% total organic carbon (TOC). Ten-cycle (10 × 20 h) accelerated fouling test demonstrated approximately 30% flux decline in association with Si-containing foulants, which could be removed almost completely through OB with 97.1% flux recovery. This study provides a proof-of-concept demonstration of FO for volume reduction and water reclamation of ROC produced from CCI, making the treatment of ROC more efficient and more energy effective.

  • Reverse osmosis concentrate from coal chemical industry treated by forward osmosis.

  • A flux of 26.4 LMH and water recovery of 92.5% were achieved.

  • Specific energy consumption for water reclamation was as low as 0.050 kWh·m−3.

  • 97.1% flux recovery was obtained by osmotic backwash after membrane fouling.

The coal chemical industry (CCI) is developing rapidly and demands tremendous water consumption (Li et al. 2015; Jia et al. 2016). CCI is also characterized as pollution-intensive for high strength wastewater, which contains a large number of hazardous organic substances with high COD value and chromaticity (Wang & Han 2012; Chen et al. 2019b). After pretreatment, biological and advanced treatment of the process wastewater, the effluent together with the saline wastewater produced from the circulating water system and desalination process is generally further treated by using ultrafiltration and reverse osmosis (UF + RO double-membrane process) for water reuse purposes (Zhu et al. 2018). However, the double-membrane process can only recover water with limited efficiency; that is, 40–85%, and thus leaves RO concentrate (ROC) with refractory organic pollutants and total dissolved solids (TDS) on the order of magnitude of ∼104 mg·L−1 (Pramanik et al. 2017). Adopting the evaporation pond for ROC final disposal will lead to 15–60% waste of water resources and potential risk of groundwater contamination (Katzir et al. 2012). Therefore, more efficient strategies are required for ROC volume reduction, water reclamation, and decontamination.

Both thermal and membrane-based processes have been developed for ROC volume reduction and zero liquid discharge (ZLD) in recent years (Tong & Elimelech 2016). Thermal processes working upon a brine concentrator and a brine crystallizer are generally expensive and energy-intensive (McGinnis et al. 2013). In comparison, a membrane-based process; that is, the secondary RO in this case, does not require phase transition for separation, making it more energy effective than a thermal process (Elimelech & Phillip 2011). Whereas, practical application of RO appears to be inherently hindered by serious membrane fouling and the upper limitation of external pressure that can be applied to the system. In recent years, electric voltage driven electrodialysis (ED) and hydrophobic membrane-based membrane distillation (MD) have emerged for volume reduction of ROC. Nevertheless, ED and MD are constrained by issues associated with membrane fouling (Korngold et al. 2009; Naidu et al. 2017) and passage of volatile pollutants into the permeate (Shaffer et al. 2013).

In FO, water molecules are transported across the semi-permeable membrane from the feed solution (FS) to the draw solution (DS) driven by osmotic pressure difference, while other components are non-permeable (Cath et al. 2006; Zhao et al. 2012). Without external pressure, FO is more attractive by virtue of less energy input, lower membrane fouling, and the loosely packed fouling layer (Shaffer et al. 2015). Up to now, FO has been extensively investigated for various applications including wastewater treatment (Sun et al. 2018; Gao et al. 2019; Maknakorn et al. 2019), liquid food concentration (Rastogi 2016; Menchik & Moraru 2019) and seawater/brackish water desalination (Chen et al. 2019a; Giagnorio et al. 2019).

Forward osmosis has also been successfully adopted for minimization of ROC from water reclamation plants (Kazner et al. 2014; Jamil et al. 2015, 2016) and groundwater desalting facilities (Martinetti et al. 2009; Wang et al. 2016; Li et al. 2019). It is noteworthy that the ROC used in these studies was either low in TDS (<3,000 mg·L−1) (Kazner et al. 2014; Jamil et al. 2015, 2016) or low in TOC (0.19 mg·L−1) (Wang et al. 2016). In addition, Wang et al. demonstrated the potential of FO in treating ROC (TDS of 5,800 mg·L−1 and TOC of 200 mg·L−1) from textile wastewater (Wang et al. 2020). However, to the best of our knowledge, there are no reports of CCI ROC minimization by FO.

Although FO is considered to be a membrane technology with low fouling risk, membrane fouling of the FS side was observed in most of the studies, causing flux decline and membrane deterioration (Martinetti et al. 2009; Kazner et al. 2014; Jamil et al. 2015, 2016; Wang et al. 2020). Osmotic backwash (OB), which utilizes osmotically induced reverse permeate flow to remove the foulants in the membrane pores and to lift the cake layer, has been proved as an efficient cleaning method to restore the membrane performance (Martinetti et al. 2009; Yip & Elimelech 2013; Motsa et al. 2017; Haupt & Lerch 2018).

In this paper, FO with a commercially available membrane was adopted to evaluate the feasibility of CCI ROC volume reduction. The effects of membrane orientation and DS concentration on the FO performance were investigated. The volume reduction capacity of FO was determined via extended period tests and the specific energy consumption was calculated. To eliminate the membrane fouling, the fouling layer was characterized and OB was assessed for membrane cleaning with comparison to two traditional methods, namely, physical cleaning and chemical cleaning.

ROC from CCI plant as FS

The ROC used for the current study was collected from a CCI plant in Heilongjiang Province. In this plant, mixed wastewater from the coal gasification process and coal coking process are treated successively through pretreatment, biological process, and advanced treatment. Afterwards, the effluent and saline wastewater are subjected to a UF + RO double-membrane process for water reclamation. ROC was sampled from the brine stream exiting the RO facility. Table 1 displays the main characteristics of the ROC water samples.

Table 1

Major water quality parameters of CCI ROC

ParameterUnitValue
TDS mg·L−1 12,800 
COD mg·L−1 250 
TOC mg·L−1 70 
pH  7.1 
Na+ mg·L−1 3,800 
Ca2+ mg·L−1 80 
Mg2+ mg·L−1 100 
SO42− mg·L−1 3,100 
Cl mg·L−1 5,100 
SiO2 mg·L−1 40 
Osmotic pressure bar 4.8 
ParameterUnitValue
TDS mg·L−1 12,800 
COD mg·L−1 250 
TOC mg·L−1 70 
pH  7.1 
Na+ mg·L−1 3,800 
Ca2+ mg·L−1 80 
Mg2+ mg·L−1 100 
SO42− mg·L−1 3,100 
Cl mg·L−1 5,100 
SiO2 mg·L−1 40 
Osmotic pressure bar 4.8 

Membrane and chemicals

The FO membrane used in the current study was provided by Fluid Technology Solutions (FTS-H2O, USA) and consists of an active rejection layer made of cellulose triacetate (CTA) as well as a polyester support layer. Basic parameters and guidelines of the membrane are provided in Table S1 (Supplementary Data). NaCl was adopted as the DS. DS and the cleaning solution used in OB were prepared by dissolving NaCl in DI water, and HCl solution (pH = 3) by diluting the concentrated HCl with DI water. All the chemicals used are of analytical grade and were provided by Damao Chemical Reagent Factory, Tianjin, China. DI water was produced by PureLab Prima (ELGA LabWater, UK).

FO operation

FO experiments were conducted with a laboratory-scale membrane module (Figure S1 Supplementary Data) as described in our previous study (You et al. 2012). The membrane was sealed by rubber gaskets between the DS channel and FS channel, which are designed to have a size of 7.2 cm × 3.5 cm × 0.7 cm with an effective membrane area of 25.2 cm2. Both AL-FS mode (active layer facing FS) and AL-DS mode (active layer facing DS) were evaluated. DS and FS flowed concurrently (200 mL·min−1) in the channels, assisted by two peristaltic pumps (WT600-2 J, LongerPump, Baoding, China). The system maintained a constant temperature (25 ± 1 °C) via a thermostatic bath (DC-0510, Scientz, Ningbo, China) and the weight of DS was recorded at regular intervals by an electronic balance (DT5000A, Xinsheng, Shanghai, China), which was connected to a computer.

The FO water flux Jw (L·m−2·h−1, LMH) was calculated based on Equation (1), considering the density of water to be 1.0 kg·L−1 (McCutcheon et al. 2005).
(1)
where ΔV (L) is the volume change of DS, Am (m2) the effective membrane surface area and t (h) the experiment time. The rejection rate was obtained using the following equation (McCutcheon et al. 2005; You et al. 2017):
(2)
where C0 (mg·L−1) is the initial FS concentration, Ct (mg·L−1) the FS concentration after t, V0 (mL) the initial FS volume and Vt (mL) the FS volume after t. The recovery was calculated as (Singh et al. 2019):
(3)

Energy consumption estimation

In the FO process including DS regeneration, the recirculation energy of pumps is observed to account for 25–30% of the total demand, while the rest (70–75%) was mainly consumed by DS regeneration (Zou et al. 2016). The specific energy consumption (SEC) of the whole FO process is then calculated via the pump recirculation energy (Lambrechts & Sheldon 2019) divided by 25%:
(4)
(5)
where Ppump (kW) is the power of the pumps, ηv (0.85–0.95, taking 0.90) and ηm (0.80–0.90, taking 0.85) the volumetric efficiency and mechanical efficiency of the pump, respectively, ηM (0.85) the efficiency of the pump motor, Qs (m3·h−1) the volumetric flow rate of DS and FS, Qp (m3·h−1) the volumetric flow rate of the permeate, ρ (1,000 kg·m−3) the density of water, g (m·s−2) the gravitational acceleration, H (m) the total head of the pump, 25% the percentage taken for recirculation energy and 3.6 × 106 the conversion factor between kWh and J.

Cleaning strategies

During OB, DI and NaCl solution (4 M) were introduced to the DS side and the FS side, respectively, with the same flow rate as that in the fouling experiments. Since the osmotic pressure gradient was in the opposite direction compared with the FO process, water moved across the membrane from DS to FS, which enabled pore flushing and cake layer lifting (Motsa et al. 2017). For physical cleaning, DI water circulated on both sides of the membrane with a flow rate twice as large as that in the fouling experiments. As for chemical cleaning, HCl is considered to be efficient for inorganic foulant removal and pH of 3–7 is recommended for CTA membrane operation by the manufacturer, so HCl solution (pH = 3) was used to remove the foulants on the membrane surface on the FS side while DI was circulated on the DS side.

Characterization

The concentration of anions and cations was determined by ion chromatography (Dionex Integrion HPIC, Thermo Fisher Scientific, USA) and inductively coupled plasma optical emission spectrometry (ICP-OES, Optima 5300 DV, PerkinElmer, USA). pH and TDS values were obtained by a pH detector (FiveEasy, Mettler Toledo, Switzerland) and a conductivity meter (CON 2700, Eutech Instruments, Thermo Fisher Scientific, USA). TOC values were measured by a TOC analyzer (TOC-VCPN, Shimadzu, Japan). The osmotic pressure of FS and DS was calculated by OLI System software.

Morphology of the membrane and the fouling layer was observed with a scanning electron microscope (SEM, Sigma 500, Zeiss, German) and an atomic force microscope (AFM, Dimension Icon, Bruker, German), while the chemical and elemental compositions of the fouling layer were provided by Fourier-transform infrared spectroscopy (FTIR, Spectrum One, PerkinElmer, USA) and X-ray energy dispersive spectrometry (EDS, X-MAX 50, Oxford, UK). All the membrane samples were dried in an oven for at least 24 h before these measurements.

Effects of DS concentration and membrane orientation

The flux data were obtained under both modes at various DS concentrations; namely, 0.5 M (24.6 bar), 1.0 M (51.6 bar), 2.0 M (13.8 bar), 3.0 M (186.7 bar) and 4.0 M (270.5 bar). With the elevation of the DS concentration from 0.5 M to 4.0 M, the flux increased from 5.3 LMH to 14.8 LMH (179% increase) for AL-DS mode and from 6.4 LMH to 26.4 LMH (313% increase) for AL-FS mode (Figure 1(a)), mainly as a result of increased driving force. In addition, slower increase with DS concentration was observed for both modes due to the combined effects of concentration polarization (CP) and reverse salt flux (McCutcheon & Elimelech 2006).

Figure 1

(a) Flux as a function of osmotic pressure of DS, (b) AFM images of active layer and support layer for a new membrane, (c) cyclic experiments, (d) photographs and SEM images of the FO membranes. ROC from a local CCI plant was used as FS (500 mL) and NaCl solution of various concentrations served as DS (500 mL). Batch mode tests were conducted for 1 h to obtain the flux values. During the cyclic experiments, the experiment was conducted under both AL-FS mode and AL-DS mode for five continuous cycles (5 × 4 h) using 4 M NaCl as DS. The system was emptied and replenished with fresh DS (500 mL) and FS (500 mL) after each cycle. Photographs of the membranes were taken after the cyclic experiments with SEM images of the active layer (AL-FS mode) and the support layer (AL-DS mode).

Figure 1

(a) Flux as a function of osmotic pressure of DS, (b) AFM images of active layer and support layer for a new membrane, (c) cyclic experiments, (d) photographs and SEM images of the FO membranes. ROC from a local CCI plant was used as FS (500 mL) and NaCl solution of various concentrations served as DS (500 mL). Batch mode tests were conducted for 1 h to obtain the flux values. During the cyclic experiments, the experiment was conducted under both AL-FS mode and AL-DS mode for five continuous cycles (5 × 4 h) using 4 M NaCl as DS. The system was emptied and replenished with fresh DS (500 mL) and FS (500 mL) after each cycle. Photographs of the membranes were taken after the cyclic experiments with SEM images of the active layer (AL-FS mode) and the support layer (AL-DS mode).

Close modal

It is also observed that the flux under AL-DS mode is much lower than under AL-FS mode, especially in the range of higher DS concentration. On the one hand, since the support layer has a rougher surface (Rq = 12.3, Ra = 9.85) than the active layer (Rq = 2.44, Ra = 1.82), as is shown in Figure 1(b), the foulants in FS would accumulate more easily on the rougher support layer (cake formation) under AL-DS mode. On the other hand, the foulants could enter the porous structure of the support layer (pore blocking) under AL-DS mode, impeding the water permeation and increasing the mass transfer resistance for the salt ions, leading to more serious CP. Furthermore, faster water permeation under higher DS concentration leads to a larger drag force of foulants to the membrane, thus accelerating both cake formation and pore blocking. Compared with the relatively clean membrane under AL-FS mode after 1 h operation, a much darker color was observed for AL-DS mode, indicating more serious fouling (Figure S2).

Although it is common practice to employ AL-FS mode for FO, AL-DS mode is favored by pressure retarded osmosis (PRO) using seawater/river water for energy harvest (Chou et al. 2012; Han et al. 2013) as well as applications where FS has relatively low fouling propensity (Kim et al. 2018). To further examine the effect of membrane orientation on long-term FO performance, the experiment was conducted under both modes for five continuous cycles (5 × 4 h) using 4 M NaCl as DS (Figure 1(c)). The initial water flux under AL-DS mode (10.9–18.4 LMH) is much lower compared with AL-FS mode (27.2–28.2 LMH), which is consistent with the results in Figure 1(a). The flux decline within a single cycle was mainly ascribed to the decrease of osmotic pressure difference, since the present study allowed the dilution of DS (osmotic dilution mode) instead of keeping a constant DS concentration (constant DS mode). In comparison, the flux difference between different cycles showed the sole effect of membrane fouling. As we can see, the initial flux declined by about 4% (from 28.2 to 27.2 LMH) after five cycles for AL-FS mode, while 41% (from 18.4 to 10.9 LMH) for AL-DS mode, indicating fast and severe foulant accumulation on the membrane surface and in the porous structure.

The membrane had a much darker color under AL-DS mode than under AL-FS mode after the cyclic experiments, whereas the SEM images showed no obvious difference of foulant accumulation on the membrane surface between the two modes (Figure 1(d)). Therefore, the inferiority of AL-DS mode in the present study is considered mainly derived from pore blocking instead of cake formation. According to the above results, AL-DS mode is unsuitable for CCI ROC volume reduction by FO and AL-FS mode is employed for the following experiments.

To ensure good quality of product water, we also determined the rejection of TOC, SO42−, Mg2+, Ca2+, and Si (Figure 2) under different DS concentrations. The membrane could reject more than 98% of SO42−, Mg2+ and Ca2+ with negligible effects of DS concentration on the rejection rates. As for Si, a little lower rejection (92–98%) was observed because Si was a major component of the fouling layer (which will be discussed later in this study) and the rejection was calculated using the FS concentration (Ct) after FO treatment (Equation (2)). In contrast, only 33–55% of TOC was rejected due to the existence of small neutral organics in ROC (Alturki et al. 2013; Werber et al. 2016; Zheng et al. 2019). Since the penetration of TOC will deteriorate the product quality, we need to utilize proper technologies before FO to lower the contents of TOC and other hazardous substances, especially when considering salt recovery.

Figure 2

Rejection of TOC, SO42−, Mg2+, Ca2+ and Si under various DS concentrations. The rejection rate was calculated after 250 mL permeate was collected on the DS side.

Figure 2

Rejection of TOC, SO42−, Mg2+, Ca2+ and Si under various DS concentrations. The rejection rate was calculated after 250 mL permeate was collected on the DS side.

Close modal

Volume reduction and energy consumption

Unlike RO, in which the highest salinity of treated water is restricted by RO equipment and the upper level of feasible applied pressure, FO is able to attain a larger extent of volume reduction with appropriate DS. In this part, FO was operated for extended periods to further reduce the volume of ROC and reclaim more water. To be specific, the FO system recovered 72.1% (1 M), 84.3% (2 M), 90.9% (3 M) and 92.5% (4 M) of water from FS (Figure 3(a)). The recovery rates obtained in the experiment were slightly lower than the theoretical values represented by the dashed lines, which is due to the assumptions made and the fact that osmotic pressure equilibrium across the membrane was not yet achieved. Besides, constant DS mode displayed higher theoretical recovery than osmotic dilution mode, since the former maintained the initial osmotic pressure throughout the operation, which resembled the continuous flow operation in practical applications. The flux declined gradually with increased recovery caused by both the decrease of osmotic pressure difference and membrane fouling; in addition, dramatic flux decline was observed beyond 80% recovery for 2/3/4 M due to the relatively large degree of volume reduction (Figure 3(b)). As we can expect, a higher recovery rate and a faster water reclamation are achievable by utilizing a higher initial osmotic pressure of DS. However, further elevation of recovery rate to values close to 100% leads to a dramatic increase of osmotic pressure, thus requiring a large dose of DS solutes. Therefore, a tradeoff between water reclamation and chemical dosage needs to be considered under practical situations.

Figure 3

(a) Maximum recovery and (b) flux obtained for extended hours under osmotic dilution mode. Both DS and FS have a volume of 1 L. The maximum recovery values for 1 M, 2 M, 3 M and 4 M were determined when the flux became lower than 2 LMH. The dashed lines represent the theoretical maximum recovery of osmotic dilution mode and constant DS mode assuming that the osmotic pressure of DS/FS changes linearly with the volume of DS/FS and that the end point comes when the osmotic pressures on both sides are the same. The curves start at 4.8 bar with 0% recovery and end at the saturation concentration (about 5.4 M, 406 bar) of NaCl at 20 °C.

Figure 3

(a) Maximum recovery and (b) flux obtained for extended hours under osmotic dilution mode. Both DS and FS have a volume of 1 L. The maximum recovery values for 1 M, 2 M, 3 M and 4 M were determined when the flux became lower than 2 LMH. The dashed lines represent the theoretical maximum recovery of osmotic dilution mode and constant DS mode assuming that the osmotic pressure of DS/FS changes linearly with the volume of DS/FS and that the end point comes when the osmotic pressures on both sides are the same. The curves start at 4.8 bar with 0% recovery and end at the saturation concentration (about 5.4 M, 406 bar) of NaCl at 20 °C.

Close modal

In this part, TDS of the FS increased from 1.3 g·L−1 to 4.6 g·L−1 using DS of 1 M NaCl and further increased to 17.4 g·L−1 with 4 M NaCl, indicating that FO possesses a volume reduction capacity similar to a brine concentrator, which is much higher than RO or mechanical vapor compression (Figure 4). As to the energy consumption of the current FO process with possible DS regeneration, 1 M NaCl resulted in an SEC of 0.105 kWh·m−3, which declined to 0.065 kWh·m−3, 0.056 kWh·m−3 and 0.050 kWh·m−3 for 2 M, 3 M and 4 M, respectively, making FO much more energy efficient compared with other brine concentration technologies (Figure 4). As presented by Equation (4), a higher DS concentration produces a higher Jw and thus a larger Qp, which in turn leads to a lower SEC at fixed Ppump. Similar SEC values for FO were previously reported in a study by Lambrechts et al. (Lambrechts & Sheldon 2019). According to the above results, FO is capable of replacing the brine concentrator for ROC volume reduction with very low energy consumption compared with other technologies, meanwhile significantly cutting down the equipment investment. By using CO2-NH3 DS of higher concentration with waste heat for DS regeneration, a much larger potential is expected for water reclamation by FO. Although in practice, the system will not work under the maximum recovery condition, FO could still largely reduce the volume of ROC as well as the size of the subsequent concentrator with relatively low energy consumption.

Figure 4

Brine concentration technologies (adapted from GWI Produced Water Report, 2011).

Figure 4

Brine concentration technologies (adapted from GWI Produced Water Report, 2011).

Close modal

Fouling characteristics and cleaning strategies

To understand the fouling characteristics of the FO membrane during volume reduction of ROC, accelerated fouling experiments were run for ten cycles (10 × 20 h) with DS of 4 M NaCl, after which the flux declined by about 30% (Figure S3). Then, we employed one of the cleaning methods for 1 h to remove the foulants on the membrane.

Figure 5 displays the photographs of the new membrane, fouled membrane and membranes after cleaning. The covered parts represent areas on the membrane that are covered by foulants visible to the naked eye, while the uncovered parts represent the other areas. The percentages of covered parts and uncovered parts were calculated by an image processing software and are shown in Figure S4. As we can see, the membrane was completely covered by foulants with a dark brown color after the ten-cycle experiment, and the flux declined to 69.1% of the initial value (Figure 6). During chemical cleaning, only about 9% of foulants were removed with a recovered flux of 73.1%, which, however, is most likely to be the result of shear force instead of chemical interaction. Physical cleaning with a higher flow rate was able to wash away 37% of the foulants, restoring 92.6% of the initial flux due to an enhanced shear force on the membrane surface. During OB, water permeates through the membrane from the DS side to the FS side, pushing out the foulants in the micropores as well as exerting a lifting effect on the fouling layer, which could then be washed away by the influent. A recovered flux of 97.1% was achieved by OB, and only 20% of foulants remained due to poor hydraulic conditions near the membrane edges. Therefore, the foulants were removed from the membrane surface, mainly due to hydraulic interaction between the foulants and the influent, while HCl showed insignificant effect on the removal of Si-dominated foulants (details discussed later in the paper). Since physical cleaning adopted a higher flow rate, better cleaning efficiency was achieved compared with chemical cleaning. Although OB utilized a lower flow rate, the reverse permeate flow induced by the osmotic pressure difference exerted a lifting effect on the fouling layer, weakening the foulant adsorption on the membrane, which contributed to an even stronger overall hydraulic interaction and thus a higher cleaning efficiency.

Figure 5

Photographs of (a) the new membrane, (b) the fouled membrane and membranes after (c) chemical cleaning, (d) physical cleaning and (e) OB (black square: uncovered parts; white circle: covered parts).

Figure 5

Photographs of (a) the new membrane, (b) the fouled membrane and membranes after (c) chemical cleaning, (d) physical cleaning and (e) OB (black square: uncovered parts; white circle: covered parts).

Close modal
Figure 6

Normalized flux of the new membrane, fouled membrane and flux after membrane cleaning.

Figure 6

Normalized flux of the new membrane, fouled membrane and flux after membrane cleaning.

Close modal

In order to understand the properties of the fouling layer, the morphology and elemental composition were obtained via SEM-EDS. As is shown in Figure 7(a), the surface of the new membrane is smooth and clean, while the slightly bulgy parts originate from the embedded polyester mesh. The atomic ratio of C/O is 68.5:31.5, which is a reasonable value contributed to by both the polyester support layer and CTA active layer. In contrast, the fouled membrane has a very rough surface (Figure 7(b)), indicating a complete coverage of the foulants, which would significantly compromise the FO performance. According to the EDS results of the fouled membrane, At% of O rises to 42.6%, while At% of C declines to 29.2%, with the emergence of a similar amount of Si (27.3%). Besides, S, Mg and Ca account for 0.9% in total.

Figure 7

SEM-EDS results of (a) new and (b) fouled membranes (the inset shows the atomic percentage, At%), SEM images and C:O:Si ratios of (c) the covered parts and (d) the uncovered parts after chemical cleaning, physical cleaning and OB. f, c, p, o and n represent fouled membrane, chemical cleaning, physical cleaning, OB and new membrane, respectively.

Figure 7

SEM-EDS results of (a) new and (b) fouled membranes (the inset shows the atomic percentage, At%), SEM images and C:O:Si ratios of (c) the covered parts and (d) the uncovered parts after chemical cleaning, physical cleaning and OB. f, c, p, o and n represent fouled membrane, chemical cleaning, physical cleaning, OB and new membrane, respectively.

Close modal

The changes of surface properties due to the foulant accumulation were further investigated via FTIR. The results illustrated absorption peaks (C = O, C-O-H, and C-O-C) characteristic of the CTA membrane structure for the new membrane (Figure S5). However, these peaks show lower or negligible intensity for the fouled membrane, indicating significant foulant adsorption on the membrane. Meanwhile, the foulants are further identified by the emergence of Si-O-Si absorption peaks, which is consistent with the EDS results in Figure 7(b), where a significant rise of At% is observed for O and Si. Since Si comes from the foulants instead of the membrane and the amount of Si is much larger than S, Mg and Ca, the C:O:Si ratio could serve as an indicator in this study to determine the degree of fouling and the efficiency of cleaning.

To further evaluate the cleaning efficiency of the three approaches, attention was paid to the covered parts and the uncovered parts. Since the new membrane is uncovered with 100% of initial flux and the fouled membrane is fully covered with 69.1% of initial flux, we can assume that the uncovered parts have a flux of 100% and covered parts 69.1%. Then, we can obtain the calculated fluxc after membrane cleaning according to the area percentages (Figure S4) and compare it with the real flux values fluxr in order to determine the permeability change of the fouling layer. For chemical cleaning, the real normalized flux (fluxr) is similar to fluxc, which means that the covered parts remained unchanged after chemical cleaning. In contrast, fluxr is much larger than fluxc after physical cleaning and OB, indicating less foulant accumulation and significantly restored water permeation at the covered parts (considering the lower percentage of covered parts for OB). Figure 7(c) and 7(d) display the SEM-EDS results of the covered and uncovered parts. After chemical cleaning and physical cleaning, the covered parts showed similar morphology and C:O:Si ratios to the fouled membrane. In contrast, only small amounts of foulants were adsorbed on the membrane after OB and the C:O:Si ratio is close to that of the new membrane. As for the uncovered parts, visible foulants remained on the membrane after chemical cleaning, while no obvious foulant accumulation was observed after OB and physical cleaning, and the C:O:Si ratios are nearly the same as that of the new membrane. Thus, OB was further proved to be an efficient cleaning method for CCI ROC volume reduction by FO.

This study investigated the potential of the FO process for volume reduction and water reclamation of CCI ROC. AL-FS mode outperformed AL-DS mode and achieved a flux of 26.4 LMH and a recovery rate of 92.5% at a DS concentration of 4 M NaCl with energy consumption of 0.050 kWh·m−3. A flux decline appeared in long-term treatment of ROC mainly due to the formation of Si-containing foulants, which, however, could be removed almost completely by OB owing to the synergistic effect by hydraulic shear force of the influent and lifting force of the reverse permeate flow. FO was proved to be an effective technology for volume reduction of CCI ROC, with OB acting as a promising cleaning method. For the ongoing and upcoming studies, proper pretreatment of ROC needs to be investigated for improved FO performance and better quality of product water. The fouling characteristics in accelerated fouling experiments may be different from real applications, so we still need to explore a suitable chemical cleaning method and combine it with OB to facilitate the foulant removal in real applications.

This work was supported by the National Key Technology R&D Program (No. 2019YFC0408503) and State Key Laboratory of Urban Water Resource and Environment (No. 20180X09).

All relevant data are included in the paper or its Supplementary Information.

Alturki
A. A.
McDonald
J. A.
Khan
S. J.
Price
W. E.
Nghiem
L. D.
Elimelech
M.
2013
Removal of trace organic contaminants by the forward osmosis process
.
Sep. Purif. Technol.
103
,
258
266
.
https://doi.org/10.1016/j.seppur.2012.10.036
.
Cath
T. Y.
Childress
A. E.
Elimelech
M.
2006
Forward osmosis: principles, applications, and recent developments
.
J. Membr. Sci.
281
(
1
),
70
87
.
https://doi.org/10.1016/j.memsci.2006.05.048
.
Chen
Q.
Ge
Q.
Xu
W.
Pan
W.
2019a
Functionalized imidazolium ionic liquids promote seawater desalination through forward osmosis
.
J. Membr. Sci.
574
,
10
16
.
https://doi.org/10.1016/j.memsci.2018.11.078
.
Chen
X.
Sun
X.
Wang
X.
Xu
P.
Yang
C.
Lu
Q.
Wang
S.
2019b
Two-stage air stripping combined with hydrolysis acidification process for coal gasification wastewater pretreatment
.
Water Sci. Technol.
79
(
11
),
2185
2194
.
https://doi.org/10.2166/wst.2019.219
.
Chou
S. R.
Wang
R.
Shi
L.
She
Q. H.
Tang
C. Y.
Fane
A. G.
2012
Thin-film composite hollow fiber membranes for pressure retarded osmosis (PRO) process with high power density
.
J. Membr. Sci.
389
,
25
33
.
https://doi.org/10.1016/j.memsci.2011.10.002
.
Elimelech
M.
Phillip
W. A.
2011
The future of seawater desalination: energy, technology, and the environment
.
Science
333
(
6043
),
712
717
.
https://doi.org/10.1126/science.1200488
.
Gao
Y.
Fang
Z.
Liang
P.
Zhang
X.
Qiu
Y.
Kimura
K.
Huang
X.
2019
Anaerobic digestion performance of concentrated municipal sewage by forward osmosis membrane: focus on the impact of salt and ammonia nitrogen
.
Bioresour. Technol.
276
,
204
210
.
https://doi.org/10.1016/j.biortech.2019.01.016
.
Giagnorio
M.
Ricceri
F.
Tiraferri
A.
2019
Desalination of brackish groundwater and reuse of wastewater by forward osmosis coupled with nanofiltration for draw solution recovery
.
Water Res.
153
,
134
143
.
https://doi.org/10.1016/j.watres.2019.01.014
.
Han
G.
Zhang
S.
Li
X.
Chung
T. S.
2013
High performance thin film composite pressure retarded osmosis (PRO) membranes for renewable salinity-gradient energy generation
.
J. Membr. Sci.
440
,
108
121
.
https://doi.org/10.1016/j.memsci.2013.04.001
.
Jamil
S.
Loganathan
P.
Kazner
C.
Vigneswaran
S.
2015
Forward osmosis treatment for volume minimisation of reverse osmosis concentrate from a water reclamation plant and removal of organic micropollutants
.
Desalination
372
,
32
38
.
https://doi.org/10.1016/j.desal.2015.06.013
.
Jamil
S.
Jeong
S.
Vigneswaran
S.
2016
Application of pressure assisted forward osmosis for water purification and reuse of reverse osmosis concentrate from a water reclamation plant
.
Sep. Purif. Technol.
171
,
182
190
.
https://doi.org/10.1016/j.seppur.2016.07.036
.
Jia
S.
Zhuang
H.
Han
H.
Wang
F.
2016
Application of industrial ecology in water utilization of coal chemical industry: a case study in Erdos, China
.
J. Clean. Prod.
135
,
20
29
.
https://doi.org/10.1016/j.jclepro.2016.06.076
.
Katzir
L.
Volkmann
Y.
Daltrophe
N.
Korngold
E.
Mesalem
R.
Oren
Y.
Gilron
J.
2012
WAIV – wind aided intensified evaporation for brine volume reduction and generating mineral byproducts
.
Desalin. Water Treat.
13
(
1–3
),
63
73
.
https://doi.org/10.5004/dwt.2010.772
.
Kazner
C.
Jamil
S.
Phuntsho
S.
Shon
H. K.
Wintgens
T.
Vigneswaran
S.
2014
Forward osmosis for the treatment of reverse osmosis concentrate from water reclamation: process performance and fouling control
.
Water Sci. Technol.
69
(
12
),
2431
2437
.
https://doi.org/10.2166/wst.2014.138
.
Kim
D. I.
Choi
J.
Hong
S.
2018
Evaluation on suitability of osmotic dewatering through forward osmosis (FO) for xylose concentration
.
Sep. Purif. Technol.
191
,
225
232
.
https://doi.org/10.1016/j.seppur.2017.09.036
.
Korngold
E.
Aronov
L.
Daltrophe
N.
2009
Electrodialysis of brine solutions discharged from an RO plant
.
Desalination
242
(
1–3
),
215
227
.
https://doi.org/10.1016/j.desal.2008.04.008
.
Li
Q.
Wei
Y.-N.
Chen
Z.-A.
2015
Water-CCUS nexus: challenges and opportunities of China's coal chemical industry
.
Clean Technol. Environ.
18
(
3
),
775
786
.
https://doi.org/10.1007/s10098-015-1049-z
.
Li
X.
Hasson
D.
Semiat
R.
Shemer
H.
2019
Intermediate concentrate demineralization techniques for enhanced brackish water reverse osmosis water recovery – a review
.
Desalination
466
,
24
35
.
https://doi.org/10.1016/j.desal.2019.05.004
.
Maknakorn
W.
Jutaporn
P.
Khongnakorn
W.
2019
Coagulation and adsorption as pretreatments of thin-film composite-forward osmosis (TFC-FO) for ink printing wastewater treatment
.
Water Sci. Technol.
79
(
5
),
877
887
.
https://doi.org/10.2166/wst.2019.100
.
Martinetti
C. R.
Childress
A. E.
Cath
T. Y.
2009
High recovery of concentrated RO brines using forward osmosis and membrane distillation
.
J. Membr. Sci.
331
(
1–2
),
31
39
.
https://doi.org/10.1016/j.memsci.2009.01.003
.
McCutcheon
J. R.
Elimelech
M.
2006
Influence of concentrative and dilutive internal concentration polarization on flux behavior in forward osmosis
.
J. Membr. Sci.
284
(
1
),
237
247
.
https://doi.org/10.1016/j.memsci.2006.07.049
.
McCutcheon
J. R.
McGinnis
R. L.
Elimelech
M.
2005
A novel ammonia-carbon dioxide forward (direct) osmosis desalination process
.
Desalination
174
(
1
),
1
11
.
https://doi.org/10.1016/j.desal.2004.11.002
.
McGinnis
R. L.
Hancock
N. T.
Nowosielski-Slepowron
M. S.
McGurgan
G. D.
2013
Pilot demonstration of the NH3/CO2 forward osmosis desalination process on high salinity brines
.
Desalination
312
,
67
74
.
https://doi.org/10.1016/j.desal.2012.11.032
.
Menchik
P.
Moraru
C. I.
2019
Nonthermal concentration of liquid foods by a combination of reverse osmosis and forward osmosis. Acid whey: a case study
.
J. Food Eng.
253
,
40
48
.
https://doi.org/10.1016/j.jfoodeng.2019.02.015
.
Motsa
M. M.
Mamba
B. B.
Thwala
J. M.
Verliefde
A. R. D.
2017
Osmotic backwash of fouled FO membranes: cleaning mechanisms and membrane surface properties after cleaning
.
Desalination
402
,
62
71
.
https://doi.org/10.1016/j.desal.2016.09.018
.
Naidu
G.
Jeong
S.
Choi
Y.
Vigneswaran
S.
2017
Membrane distillation for wastewater reverse osmosis concentrate treatment with water reuse potential
.
J. Membr. Sci.
524
,
565
575
.
https://doi.org/10.1016/j.memsci.2016.11.068
.
Pramanik
B. K.
Shu
L.
Jegatheesan
V.
2017
A review of the management and treatment of brine solutions
.
Environ. Sci-Wat. Res.
3
(
4
),
625
658
.
https://doi.org/10.1039/c6ew00339 g
.
Rastogi
N. K.
2016
Opportunities and challenges in application of forward osmosis in food processing
.
Crit. Rev. Food Sci. Nutr.
56
(
2
),
266
291
.
https://doi.org/10.1080/10408398.2012.724734
.
Shaffer
D. L.
Arias Chavez
L. H.
Ben-Sasson
M.
Romero-Vargas Castrillon
S.
Yip
N. Y.
Elimelech
M.
2013
Desalination and reuse of high-salinity shale gas produced water: drivers, technologies, and future directions
.
Environ. Sci. Technol.
47
(
17
),
9569
9583
.
https://doi.org/10.1021/es401966e
.
Shaffer
D. L.
Werber
J. R.
Jaramillo
H.
Lin
S.
Elimelech
M.
2015
Forward osmosis: where are we now?
Desalination
356
,
271
284
.
https://doi.org/10.1016/j.desal.2014.10.031
.
Singh
N.
Dhiman
S.
Basu
S.
Balakrishnan
M.
Petrinic
I.
Helix-Nielsen
C.
2019
Dewatering of sewage for nutrients and water recovery by forward osmosis (FO) using divalent draw solution
.
J. Water Process Eng.
31
,
100853
.
https://doi.org/10.1016/j.jwpe.2019.100853
.
Sun
Y.
Tian
J.
Song
L.
Gao
S.
Shi
W.
Cui
F.
2018
Dynamic changes of the fouling layer in forward osmosis based membrane processes for municipal wastewater treatment
.
J. Membr. Sci.
549
,
523
532
.
https://doi.org/10.1016/j.memsci.2017.12.055
.
Tong
T.
Elimelech
M.
2016
The global rise of zero liquid discharge for wastewater management: drivers, technologies, and future directions
.
Environ. Sci. Technol.
50
(
13
),
6846
6855
.
https://doi.org/10.1021/acs.est.6b01000
.
Wang
W.
Han
H.
2012
Recovery strategies for tackling the impact of phenolic compounds in a UASB reactor treating coal gasification wastewater
.
Bioresour. Technol.
103
(
1
),
95
100
.
https://doi.org/10.1016/j.biortech.2011.10.002
.
Wang
S.-Y.
Chen
Y.-F.
Zhou
H.
Xu
X.-H.
Cheng
L.-H.
2020
Calcium carbonate scaling in forward osmosis for textile reverse osmosis concentrate treatment
.
J. Water Process Eng.
35
,
101181
.
https://doi.org/10.1016/j.jwpe.2020.101181
.
Werber
J. R.
Deshmukh
A.
Elimelech
M.
2016
The critical need for increased selectivity, not increased water permeability, for desalination membranes
.
Environ. Sci. Tech. Let.
3
(
4
),
112
120
.
https://doi.org/10.1021/acs.estlett.6b00050
.
You
S.-J.
Wang
X.-H.
Zhong
M.
Zhong
Y.-J.
Yu
C.
Ren
N.-Q.
2012
Temperature as a factor affecting transmembrane water flux in forward osmosis: steady-state modeling and experimental validation
.
Chem. Eng. J
198–199
,
52
60
.
https://doi.org/10.1016/j.cej.2012.05.087
.
You
S.
Lu
J.
Tang
C. Y.
Wang
X.
2017
Rejection of heavy metals in acidic wastewater by a novel thin-film inorganic forward osmosis membrane
.
Chem. Eng. J.
320
,
532
538
.
https://doi.org/10.1016/j.cej.2017.03.064
.
Zhao
S.
Zou
L.
Tang
C. Y.
Mulcahy
D.
2012
Recent developments in forward osmosis: opportunities and challenges
.
J. Membr. Sci.
396
,
1
21
.
https://doi.org/10.1016/j.memsci.2011.12.023
.
Zheng
L.
Price
W. E.
McDonald
J.
Khan
S. J.
Fujioka
T.
Nghiem
L. D.
2019
New insights into the relationship between draw solution chemistry and trace organic rejection by forward osmosis
.
J. Membr. Sci.
587
,
117184
.
https://doi.org/10.1016/j.memsci.2019.117184
.
Zhu
H.
Han
Y.
Xu
C.
Han
H.
Ma
W.
2018
Overview of the state of the art of processes and technical bottlenecks for coal gasification wastewater treatment
.
Sci. Total Environ
637–638
,
1108
1126
.
https://doi.org/10.1016/j.scitotenv.2018.05.054
.
Zou
S.
Yuan
H.
Childress
A.
He
Z.
2016
Energy consumption by recirculation: a missing parameter when evaluating forward osmosis
.
Environ. Sci. Technol.
50
(
13
),
6827
6829
.
https://doi.org/10.1021/acs.est.6b02849
.

Supplementary data